Group 4 "Solar"
(cont.)
Coding in the delivered condition
Stagnation time reduction
0A:5
Temperature differential for stagna-
tion time reduction (reduction in
the speed of the solar circuit pump
to protect system components and
heat transfer medium) 5 K.
Flow rate solar circuit
0F:70
Solar circuit flow rate at the maxi-
mum pump speed 7 l/min.
Extended solar control functions
20:0
No extended control function ena-
bled
Group 5 "Heating circuit 1"
Coding
Coding in the delivered condition
Priority DHW heating
A2:2
Cylinder priority for heating circuit
pump
Min. flow temperature heating circuit
C5:20
Electronic minimum flow tempera-
ture limit 20 °C
Max. flow temperature heating circuit
C6:74
Electronic maximum flow tempera-
ture limit set to 74 °C
Pump control, heating circuit pump
F6:25
"DHW only" operating mode:
Heating circuit pump is constantly
ON.
Possible change
0A:0
Stagnation time reduction not active.
0A:1
Temperature differential adjustable
to
from 1 to 40 K.
0A:40
0F:1
Flow rate adjustable from 0.1 to
to
25.5 l/min,
0F:255
1 step
20:1
Auxiliary function for DHW heating
20:2
Differential temperature control 2.
20:3
Differential temperature control 2
and auxiliary function.
20:4
Differential temperature control 2 for
central heating backup.
20:5
Thermostat function
20:6
Thermostat function and auxiliary
function
20:7
Solar heating via external heat ex-
changer without additional tempera-
ture sensor
20:8
Solar heating via external heat ex-
changer with additional temperature
sensor
20:9
Solar heating of 2 DHW cylinders
Possible change
A2:0
Without cylinder priority for heating
circuit pump
C5:1
Minimum limit adjustable from
to
1 to 127 °C (limited by boiler-specific
C5:127
parameters)
C6:10
Maximum limit adjustable from 10 to
to
127 °C (limited by boiler-specific pa-
C6:127
rameters)
F6:0
Heating circuit pump is constantly
OFF.
F6:1
The heating circuit pump starts 1 to
to
24 times per day for 10 min each
F6:24
time.
Coding level 1
0.1 l/min.
33