Changing The Predefi Ned Parameters Set - FAAC B680H Manual

Hide thumbs Also See for B680H:
Table of Contents

Advertisement

Display
Function
Loop 2 sensitivity
S2
Adjusts the sensitivity of the vehicle detection
loop
00
Minimum sensitivity
10
Maximum sensitivity
Motor movement
Mt
Using the function provided by this parameter
makes it possible to manually move the barrier
bar, operating as dead-man. Pressing + will
open the automated system, pressing - causes
the automated system to close.
oP
pressing +, open
cL
pressing -, close
Learning
tL
Working time and limit switch learning (see
section 7.2)
AUTOMATED SYSTEM STATUS:
St
This allows you to choose whether to quit the programme
and save the data.
Y
= quit and save the data
no
= quit without saving the data
On quitting the programme, press the F key to display the
status of the automated system
00
Beam closed
01
Beam open
02
Stationary ready to open
03
Stationary ready to close
04
Automated system paused
05
Opening
06
Closing
07
Failsafe in progress
08
2-EASY device verification in progress
09
Pre-flashing then OPENS
10
Pre-flashing then CLOSES
11
EMERGENCY Open
You can go to St at any time by simultaneously pres-
sing F and -.
B680H
Displaying of the automated system status
Default
important for the installing/maintenance technician in order
to distinguish the logical processes that the board carries out
05
during movement.
If, for example, the automated system status is CLOSED, the
display MUST read
the display will change to
directly to
once the position of gate OPEN is reached).
--
Example of a status sequence displayed starting from a closed barrier
The sequence does not include statuses
correspond to pre-flashing when opening and closing,
respectively.
--
00
Beam closed
01
Beam open /
04
Pause
5.2 Changing the predefi ned parameters set
The E680 board features six sets of pre-defined configurations that
allow rapid adapting to the size of the beam installed, making it the
starting point for a fine adjustment of the parameters.
To select one of the available configurations, it is necessary to change
cF
the parameter
the barrier configuration (beam length, type and quantity of accessories
installed) given in Table 4 or Table 5 on page 25 (for example, choose
04
the default
for a beam L of 5 metres with lights and foot).
To complete configuration, it is necessary to exit the BASIC
programming menu by pressing "F" until parameter
by pressing "F" and "-"
This operation changes the value of the parameters
So
and
ADVANCED programming, setting them on the default
values as shown in the tables in paragraph 6.3.
Setting a set of pre-defi ned parameters that does not
correspond to the actual confi guration of the barrier could
cause irreversible damage to the automated system, in
particular if the default corresponds to a beam length
shorter than the actual one.
12
00
. When the OPEN command is received,
09
, if pre-fl ashing is enabled, or
05
(the OPENING movement) to then display
05
Opening
06
Closing
06
from the default value of
to that corresponding to
SC
in BASIC programming and
St
is extremely
01
09
10
and
which
St
is reached or
FO
FC
oc
,
,
in
732719 - Rev.D