Troubleshooting

Important
system is an electrical power installa-
tion and any faults must therefore be
remedied by a qualified electrician.
Fault indication
If the floor/room sensor is damaged
or interrupted, the thermostat will
cut out and the lamp start to flash
alternatingly green and red.
If the floor sensor should become
faulty, it can be replaced provided it
is installed in a spiral hose laid in the
floor as instructed. The room sensor
cannot be replaced. The thermostat
must be replaced if there is a fault
with the room sensor.
Test values for floor sensor
The following values apply when the
floor sensor's measurements are
checked.
Temperature
10
C
o
15
C
o
20
C
o
25
C
o
30
C
o
28
The underfloor heating
Resistance
18,0 kΩ
14,7 kΩ
12,1 kΩ
10,0 kΩ
8,3 kΩ