7.4.5

Offset

In order to obtain a perfect linearization of the instrument, it is recommended to make an
adjustment of the zero offset each time an installation is performed.
The flow rate must be zero, that is, the liquid inside the pipe where the flowmeter is installed
should be completely stopped. Furthermore, a completely full pipe is necessary in order to
make an effective adjustment.
When the option Offset is selected, the following screen is shown:
When the flow rate is stable, press the key (Enter) and the instrument will save the value.
7.5

Outputs

This screen allows to program the four outputs of the instrument: Relay 1, Relay 2, pulses
and analog output (4-20 mA).
7.5.1

Relay 1 and relay 2

By selecting one of the two relay outputs, next screen appears with the options which allow
to assign the relay to a function.