INSTALLATION MANUAL
1100MNGK / 1100MPGK Gas Conversion Kit
For Valor 1100M fi replaces ONLY
This appliance is certified for use from 0–4500 feet. For
altitudes above 4500 feet, see local codes.
Kit Contents
1 Pilot injector
1 Main burner injector
1 Set of conversion labels
1 Minimum rate by-pass screw
Tools Required
• Wrenches, to disconnect gas line
• Phillips (+) screwdriver
• Small (jewelers size) flat blade screwdriver, to set
pressure
• Small flat blade screwdriver, to release pressure tap
on valve
• Needle nose pliers, to remove bypass screw
• Allen key, 5/32", to change bypass screw
• Wrench, 7/16", to remove pilot hood and injector
• Socket wrench, 7/16", with extension to change main
burner injector
• Manometer, to set pressure
Specifi cations
Model
Gas
Altitude (Ft.)*
Input Maximum (Btu/h)
Input Minimum (Btu/h)
Manifold Pressure (in w.c.)
Minimum Supply Pressure (in w.c.)
Maximum Supply Pressure (in w.c.)
Main Burner Injector Marking
PSE Pilot Injector Marking
Min. Rate By-Pass Screw
4009100-01
©2021, Miles Industries Ltd.
H5 Series
1100MN
1100MP
Natural
Propane
0-4,500 feet
30,000
30,000
16,000
16,000
3.5"
9"
5"
11"
10"
14"
36 DMS
51 DMS
BL22N
BL14LP
185
125
 WARNING
This conversion kit shall be installed by
a qualified service agency in accordance
with the manufacturer's instructions and
all applicable codes and requirements
of the authority having jurisdiction. If
the information in these instructions is
not followed exactly, a fire, explosion
or production of carbon monoxide may
result causing property damage, personal
injury or loss of life. The qualified service
agency is responsible for the proper
installation of this kit. The installation
is not proper and complete until the
operation of the converted appliance is
checked as specified in the manufacturer's
instructions supplied with the kit.
Use this manual in conjunction with the
installation manual supplied with the
appliance.
General Notes Regarding Conversion
The conversion may be done before or after the
appliance is installed into the cavity. However, the gas
must be connected to set the manifold pressure.

Advertisement

loading

Summary of Contents for Valor H5 Series

  • Page 1 INSTALLATION MANUAL H5 Series 1100MNGK / 1100MPGK Gas Conversion Kit For Valor 1100M fi replaces ONLY This appliance is certified for use from 0–4500 feet. For altitudes above 4500 feet, see local codes.  WARNING Kit Contents This conversion kit shall be installed by...
  • Page 2 Prepare the appliance 6. Remove the burner module by undoing 12 screws and lifting forward and then up. Be careful not to See your Installation Manual for help with these steps. hook the aeration block above, or the control 1. If the fireplace is already installed, remove the valve below, as you pull the burner module up.
  • Page 3 Convert the pilot injector Replace the minimum rate by-pass screw 1. Remove the pilot hood using a 7/16” wrench. 1. Turn module assembly upside down, unlock and remove pipe assembly. 2. Remove the old pilot injector with needle nose pliers, or turn the pilot over and the old pilot injector will fall out.
  • Page 4 Re-assemble module Set the manifold pressure To reinstall, reverse the previous procedures. 1. Fit a manometer to the manifold pressure test tap on the valve—see figure below. 1. Position and locate module in the firebox inserting the valve first. Be careful not to trap cables Loosen screw to check (tighten afterwards) between firebox frame and module.
  • Page 5 Because our policy is one of constant development and improvement, details may vary slightly from those given in this publication. Designed and Manufactured by / for Miles Industries Ltd. 190 – 2255 Dollarton Highway, North Vancouver, B.C., CANADA V7H 3B1 Tel. 604-984-3496 Fax 604-984-0246 www.valorfi replaces.com...
  • Page 6: Guide D'installation

    GUIDE D’INSTALLATION Série H5 Trousses de conversion de gaz 1100MNGK et 1100MPGK pour foyers Valor 1100M SEULEMENT Cet appareil est homologué pour utilisation de 0 à 4 500 pieds. Pour altitudes au-dessus de 4 500 pieds,  WARNING consultez la règlementation locale.
  • Page 7 Préparez l’appareil 6. Enlevez le module du brûleur en dévissant les 12 vis le retenant; soulevez-le vers l’avant puis vers le haut 1. Si le foyer est déjà installé, enlevez le pare-étincelles, pour le sortir de la boîte de foyer. Faites attention les portes des côtés, la plinthe, la fenêtre, le lit de ne pas accrocher le bloc d’aération sur le de combustion et les panneaux de cérramique.
  • Page 8 Remplacez l’injecteur de veilleuse Remplacez la vis d’indice minimum 1. Enlevez le capuchon de la veilleuse avec une clé 1. Tournez la plaque du brûleur à l’envers; enlevez 7/16”. l’écrou de verrouillage et débranchez de le tuyau. 2. Enlevez les deux vis retenant la soupape à son support en faisant attention aux autres connexions.
  • Page 9 Réinstallez le module du brûleur Réglez et vérifi ez la pression d’admission Procédez à l’inverse pour réinstaller le brûleur. 1. Fixez un mano-mètre à la connexion de vérifica- tion de pression d’admission sur la soupape—voir 1. Placez la plaque du brûleur dans la boîte de foyer, l’image ci-dessous.
  • Page 10 Réinstallez les pièces du foyer 1. Réinstallez la paroi arrière de la boîte de foyer (6 vis). 2. Réinstallez le couvercle du brûleur (4 vis). 3. Réinstallez les panneaux intérieurs, le lit de combustion et la fenêtre. Consultez le guide d’installation du foyer pour tous les détails concernant l’installation de ces pièces.

This manual is also suitable for:

1100mngk1100mpgk