INSTALLATION MANUAL
1100MNGK / 1100MPGK Gas Conversion Kit
For Valor 1100M fi replaces ONLY
This appliance is certified for use from 0–4500 feet. For
altitudes above 4500 feet, see local codes.
Kit Contents
1 Pilot injector
1 Main burner injector
1 Set of conversion labels
1 Minimum rate by-pass screw
Tools Required
• Wrenches, to disconnect gas line
• Phillips (+) screwdriver
• Small (jewelers size) flat blade screwdriver, to set
pressure
• Small flat blade screwdriver, to release pressure tap
on valve
• Needle nose pliers, to remove bypass screw
• Allen key, 5/32", to change bypass screw
• Wrench, 7/16", to remove pilot hood and injector
• Socket wrench, 7/16", with extension to change main
burner injector
• Manometer, to set pressure
Specifi cations
Model
Gas
Altitude (Ft.)*
Input Maximum (Btu/h)
Input Minimum (Btu/h)
Manifold Pressure (in w.c.)
Minimum Supply Pressure (in w.c.)
Maximum Supply Pressure (in w.c.)
Main Burner Injector Marking
PSE Pilot Injector Marking
Min. Rate By-Pass Screw
4009100-01
©2021, Miles Industries Ltd.
H5 Series
1100MN
1100MP
Natural
Propane
0-4,500 feet
30,000
30,000
16,000
16,000
3.5"
9"
5"
11"
10"
14"
36 DMS
51 DMS
BL22N
BL14LP
185
125
WARNING
This conversion kit shall be installed by
a qualified service agency in accordance
with the manufacturer's instructions and
all applicable codes and requirements
of the authority having jurisdiction. If
the information in these instructions is
not followed exactly, a fire, explosion
or production of carbon monoxide may
result causing property damage, personal
injury or loss of life. The qualified service
agency is responsible for the proper
installation of this kit. The installation
is not proper and complete until the
operation of the converted appliance is
checked as specified in the manufacturer's
instructions supplied with the kit.
Use this manual in conjunction with the
installation manual supplied with the
appliance.
General Notes Regarding Conversion
The conversion may be done before or after the
appliance is installed into the cavity. However, the gas
must be connected to set the manifold pressure.