Particulate Contamination - Lenovo SI4091 Installation Manual

10gb system interconnect module
Table of Contents

Advertisement

Particulate Contamination

56
SI4091 10Gb System Interconnect Module Installation Guide
Attention: Airborne particulates (including metal flakes or particles) and reactive
gases acting alone or in combination with other environmental factors such as
humidity or temperature might pose a risk to the device that is described in this
document.
Risks that are posed by the presence of excessive particulate levels or
concentrations of harmful gases include damage that might cause the device to
malfunction or cease functioning altogether. This specification sets forth limits for
particulates and gases that are intended to avoid such damage. The limits must not
be viewed or used as definitive limits, because numerous other factors, such as
temperature or moisture content of the air, can influence the impact of particulates
or environmental corrosives and gaseous contaminant transfer. In the absence of
specific limits that are set forth in this document, you must implement practices
that maintain particulate and gas levels that are consistent with the protection of
human health and safety. If Lenovo determines that the levels of particulates or
gases in your environment have caused damage to the device, Lenovo may
condition provision of repair or replacement of devices or parts on implementation
of appropriate remedial measures to mitigate such environmental contamination.
Implementation of such remedial measures is a customer responsibility.
Contaminant
Limits
The room air must be continuously filtered with 40% atmospheric dust
Particulate
spot efficiency (MERV 9) according to ASHRAE Standard 52.2
Air that enters a data center must be filtered to 99.97% efficiency or
greater, using high-efficiency particulate air (HEPA) filters that meet
MIL-STD-282.
The deliquescent relative humidity of the particulate contamination
must be more than 60%
The room must be free of conductive contamination such as zinc whis-
kers.
Copper: Class G1 as per ANSI/ISA 71.04-1985
Gaseous
Silver: Corrosion rate of less than 300 Å in 30 days
1
ASHRAE 52.2-2008 - Method of Testing General Ventilation Air-Cleaning Devices for
Removal Efficiency by Particle Size. Atlanta: American Society of Heating,
Refrigerating and Air-Conditioning Engineers, Inc.
2
The deliquescent relative humidity of particulate contamination is the relative
humidity at which the dust absorbs enough water to become wet and promote
ionic conduction.
3
ANSI/ISA-71.04-1985. Environmental conditions for process measurement and
control systems: Airborne contaminants. Instrument Society of America, Research
Triangle Park, North Carolina, U.S.A.
2
.
3
1
.