Omron F10-C20 Instruction Sheet page 30

Pattern matching sensor amplifier
Hide thumbs Also See for F10-C20:
Table of Contents

Advertisement

----------------------------------------------------------------------------------------------
■ SG -System data Get- : Acquire system data
----------------------------------------------------------------------------------------------
SG  acquires  system  data  information.System  data  is  data  that  is  not
reliant on banks.
Input Command
@<unit̲number>SG̲<parameter>[CR]
・ Set the following numerical values for <unit̲number>.
・ Set the following numerical values for <parameter>.
Output Response
@<unit̲number>SG̲<value>[CR] : Executed correctly
@<unit̲number>SG̲ER[CR]
<unit̲number>
<parameter> = 0: Unit number
<value>
<parameter> = 1: Baud rate
<value>
<parameter> = 2: OFF delay timer value
<value>
 
Unit No. 
Content 
5:  100
00 to 31 
Unit number of Unit whose data is to be set. 
m
s
XX 
Used to set data of all F10's. 
6:  120
ms
<parameter> = 3: LED guide light ON/OFF
<value>
: Not executed correctly
00 to 31: Designated unit number
01 to 31: Unit number
1:  1200 bps
2:  2400 bps
3:  4800 bps
4:  9600 bps
5: 19200 bps
6: 38400 bps
1:  20 ms
2:  40 ms
3:  60 ms
4:  80 ms
7: 140 ms
8: 160 ms
0: OFF
1: ON
53
Example
T
o
 
Parameter 
Content 
Unit number 
Baud rate 
 
 
 
 
 
 
 
 
 
 
OFF delay timer value 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
3
LED guide light ON/OFF 
 
determine the state of the LED guide light of Unit 31:
Input: @31SG̲3[CR]
Output: @31SG̲0[CR]  (not lit)
----------------------------------------------------------------------------------------------
■ SS -System data Set- : Set system data
----------------------------------------------------------------------------------------------
SS changes system data settings. System data is data that is not reliant
on banks.
Input Command
@<unit̲number>SS̲<parameter>̲<value>[CR]
・ Set the following numerical values for <unit̲number>.
When XX (all Units) is specified as the unit number, the unit
Value 
Meaning 
01 to 31 
Unit number 
1200 bps 
2400 bps 
4800 bps 
9600 bps 
19200 bps 
38400 bps 
20 ms 
40 ms 
60 ms 
80 ms 
100 ms 
120 ms 
140 ms 
160 ms 
OFF 
1
ON
54