■ SG -System data Get- : Acquire system data
----------------------------------------------------------------------------------------------
SG acquires system data information.System data is data that is not
reliant on banks.
Input Command
@<unit̲number>SG̲<parameter>[CR]
・ Set the following numerical values for <unit̲number>.
・ Set the following numerical values for <parameter>.
Output Response
@<unit̲number>SG̲<value>[CR] : Executed correctly
@<unit̲number>SG̲ER[CR]
<unit̲number>
<parameter> = 0: Unit number
<value>
<parameter> = 1: Baud rate
<value>
<parameter> = 2: OFF delay timer value
<value>
Unit No.
Content
5: 100
00 to 31
Unit number of Unit whose data is to be set.
m
s
XX
Used to set data of all F10's.
6: 120
ms
<parameter> = 3: LED guide light ON/OFF
<value>
: Not executed correctly
00 to 31: Designated unit number
01 to 31: Unit number
1: 1200 bps
2: 2400 bps
3: 4800 bps
4: 9600 bps
5: 19200 bps
6: 38400 bps
1: 20 ms
2: 40 ms
3: 60 ms
4: 80 ms
7: 140 ms
8: 160 ms
0: OFF
1: ON
53
Example
T
o
Parameter
Content
0
Unit number
1
Baud rate
2
OFF delay timer value
3
LED guide light ON/OFF
determine the state of the LED guide light of Unit 31:
Input: @31SG̲3[CR]
Output: @31SG̲0[CR] (not lit)
----------------------------------------------------------------------------------------------
■ SS -System data Set- : Set system data
----------------------------------------------------------------------------------------------
SS changes system data settings. System data is data that is not reliant
on banks.
Input Command
@<unit̲number>SS̲<parameter>̲<value>[CR]
・ Set the following numerical values for <unit̲number>.
When XX (all Units) is specified as the unit number, the unit
Value
Meaning
01 to 31
Unit number
1
1200 bps
2
2400 bps
3
4800 bps
4
9600 bps
5
19200 bps
6
38400 bps
1
20 ms
2
40 ms
3
60 ms
4
80 ms
5
100 ms
6
120 ms
7
140 ms
8
160 ms
0
OFF
1
ON