ICP DAS USA tGW-700 Series User Manual page 59

Hide thumbs Also See for tGW-700 Series:
Table of Contents

Advertisement

Tiny Modbus/TCP to RTU/ASCII Gateway
Step 4: Configuring the Pair-connection (Server Mode) on the Web Server
for tGW-700#2
1. In the eSearch Utility, click the name of the second tGW-715 module (tGW-700 #2) to select it,
and then click the "Web" button to launch a browser window to connect to the web server on
the tGW-700 #2module. Alternatively, you can enter the URL for tGW-700 #2 in the address bar
of the browser.
2. When the login screen is displayed, enter the password (use the default password "admin") in
the Password field, and then click the "Submit" button to display the configuration page.
3. Click the "Port1" tab to display the Port1 Settings page.
4. Select the appropriate Baud Rate, Data Format and Modbus Protocol settings from the relevant
drop down options. The following is an example: Baud Rate (bps) "9600", Data Bits (bits) "8",
Parity "None", Stop Bits (bits) "1" and Modbus Protocol "Modbus RTU".
Refer to Figures 5-3 to 5-5 for an illustration of how to perform Steps 4-1 to 4-4 of the procedure
described above.
5. In the Pair-connection Settings area for Port1, select "Server" from the "Application Mode"
drop down options.
6. Amend any details as required and then click the "Submit" button to complete the
configuration.
Figure 5-7
Copyright © 2017 ICP DAS CO., Ltd. All Rights Reserved.
- 59 -