10.0

ADJUSTMENT

10.1

RESTRICTING VERTICAL VENTS

EN
EN
Vertical installations may display a very active fl ame. If this appearance is not desirable, the vent exit must
be restricted using a restrictor vent kit. Refer to "ACCESSORIES" in the "REPLACEMENTS" section for
the appropriate kit. This will reduce the velocity of the exhaust gases, slowing down the fl ame pattern and
creating a more traditional gentle fl ame appearance. Specifi c instructions are included with the kit.

10.2 PILOT BURNER ADJUSTMENT

Adjust the pilot screw to provide properly sized fl ame. Turn in a
clockwise direction to reduce the gas fl ow.
Check Pressure Readings:
Inlet pressure can be checked by turning screw (A) counter-
clockwise 2 or 3 turns and then placing pressure gauge tubing
over the test point. Gauge should read as described on the chart
below. Check pressure with main burner operating on "HI".
Outlet pressure can be checked the same as above using
screw (B). Gauge should read as described on the chart
below. Check pressure with main burner operating on "HI".
AFTER TAKING PRESSURE READINGS, BE SURE TO
TURN SCREWS CLOCKWISE FIRMLY TO RESEAL. DO
NOT OVERTORQUE.
Leak test with a soap and water solution.
Prior to pilot adjustment, ensure that the pilot assembly
has not been painted. If overspray or painting of the pilot
assembly has occurred remove the paint from the pilot
assembly, or replace. Fine emery
cloth or a synthetic scrub pad (such as
Scotch-Brite™) can be used to remove
the paint from the pilot hood, electrode
and fl ame sensor.
*Maximum inlet pressure not to exceed 13".
W415-1624 / D / 11.22.16
(9.5mm - 12.7mm)
Natural Gas
Natural Gas
Pressure
(inches)
(millibars)
*13"
*7"
Inlet
(MIN. 4.5")
(MIN. 11.2mb)
3.5"
Outlet
77.3
B
A
PILOT SCREW
PILOT
ELECTRODE
BURNER
3/8" - 1/2"
FLAME
SENSOR
FLAME MUST ENVELOP
UPPER 3/8" (9.5mm) TO 1/2"
(12.7mm) OF FLAME SENSOR
Propane
(inches)
17.4mb
13"
(MIN. 11")
8.7mb
10"
39.1E
Propane
(millibars)
32.4mb
(MIN. 27.4mb)
24.9mb