ED900 Setup and Troubleshooting Instructions Table of Contents Table of contents Table of contents System setup for single door installation General information 10.1 Set ED900 operator spring tension General information 10.2 Set braking circuit plug position Safety information 10.3...
CAUTION NOTICE This symbol warns of a potentially unsafe Installation on an interior building surface. procedure or situation. The ED900 with fine cover must be installed on an interior building surface. NOTICE 1.1.3 Manual storage. Draws attention to important information This document must be kept in a secure place, and presented in this document.
WARNING 2.2 Door signage requirements. Crushing hazards at door closing edges! Proper signs and labels shall be applied and maintained on the door controlled by an ED900 fine cover swing door operator. Fig. 2.1 Door closing edges •...
ED900 Setup and Troubleshooting Instructions Chapter 3 3 Technical data ED900 technical data 3.1.1 Required operating conditions. 3.1.4 Outputs Maximum wire size Ambient temperature 5 to 122 °F [-15 to 50⁰ C] 16 AWG Connector plug 1/16” Suitable for dry...
ED900 manual and automatic Low energy product modes 4.2.1 ANSI/BHMA 156.19. ED900 operators are configured to meet requirements 4.1.1 Automatic mode. of a low energy application per ANSI/BHMA A156.19, Manual mode/automatic mode parameter hd=0. Standard for Power Assist and Low Energy Power Designed if door is preferably opened automatically Operated Swinging Doors.
ED900 Setup and Troubleshooting Instructions Chapter 5 Mode switch and Exit Only switch panels Fig. 5.3.1 Fine cover Fig. 5.3.8 Optional key switch panels Mode switch, Exit Only switch, 3 position 2 position 5.3.1 Mode switch 5.3.2 Exit Only switch 5.3.3 Mode switch position descriptions.
ED900 Setup and Troubleshooting Instructions Chapter 5 Operator status LEDs Fig. 5.4.1 Operator status LEDs 5.4.1 Operator status LEDs. 1. Red LED Blinking codes are used to indicate "ln__" information (system status or operating conditions) or certain error codes "E__".
ED900 System accessories 6.2.6 Activators 6.2.1 Overview Typical activators: ED900 operators are normally used with system 1. Pushbuttons, key switches accessories available from dormakaba USA, Inc. or other 2. Access control systems manufacturers. 3. Telephone systems 6.2.2 Accessory electrical installation.
ED900 Setup and Troubleshooting Instructions Chapter 6 Terminal board interfaces Fig. 6.3.1 ED50LE and ED100LE terminal board electrical connections Green LED (Para. 5.4) Night- Activation inputs Yellow LED (Para. 5.4) Interior Exterior bank Safety sensors input Red LED (Para. 5.4)
ED900 Setup and Troubleshooting Instructions Chapter 7 7 ED900 door signage Low energy operator, ANSI/BHMA A156.19 7.1.1 Overview Fig. 7.1.1 AUTOMATIC CAUTION DOOR decal Signage and warnings are specified in ANSI /BHMA A156.19, American National Standard for AUTOMATIC Low Energy Power Operated Swinging Doors.
ED900 Setup and Troubleshooting Instructions Chapter 7 Door signage, low energy single swing door, ANSI/BHMA A156.19 Fig. 7.2.1 Knowing act device initiation of door operation Fig. 7.2.2 Push / Pull initiation of door operation Push to Operate Pull to Operate...
Page 14
ED900 Setup and Troubleshooting Instructions Chapter 7 Fig. 7.3.4 Push / Pull, pull to operate Fig. 7.3.3 Push / Pull, push to operate AUTOMATIC AUTOMATIC CAUTION CAUTION AUTOMATIC AUTOMATIC CAUTION CAUTION DOOR DOOR DOOR DOOR DD0586-010 DD0586-010 DD0586-010 DD0586-010...
ED900 Setup and Troubleshooting Instructions Chapter 8 8 AAADM Safety information label Safety information label, low energy power operated doors 8.1.1 Low energy swing door safety information label. Fig. 8.1.1 Safety Information and Annual Compliance This AAADM label outlines safety checks that should be...
ED900 Setup and Troubleshooting Instructions Chapter 9 9 Parameters ED900 – viewing and changing parameters 9.1.1 Changing parameter values. Step 1 Press right button greater than 3 s to 1. Set Mode switch to the CLOSE position. enter program mode.
Page 17
ED900 Setup and Troubleshooting Instructions Chapter 9 Table 9.3.1 Driving parameters NOTICE Driving parameter Description Driving parameters - detail. Opening speed, automatic mode Reference Appendix A. Closing speed, automatic mode Driving parameter Description Hold open time, automatic mode Opening angle, set during learning cycle...
ED900 Setup and Troubleshooting Instructions Chapter 10 10 System setup for single door installation 10.1 Set ED900 operator spring tension Table 10.1.1 Spring tension adjustment revolutions Fig. 10.1.1 Spring tension adjustment Door width Inches 1067 1219 Spring setting revolutions...
ED900 Setup and Troubleshooting Instructions Chapter 10 10.2 Set braking circuit plug position 10.2.1 Set braking circuit plug. Fig. 10.2.1 Braking circuit socket and plug, plug factory installed in pull installation location Operator braking circuit plug is positioned in its 3 pin socket for a push or pull installation.
ED900 Setup and Troubleshooting Instructions Chapter 10 10.3 Power on Fig. 10.3.1 Mode switch Conditions prior to power on. Mode switch, 1. ED900 operator is installed. 3 position Close 2. Standard push arm or arm with track is installed.
ED900 Setup and Troubleshooting Instructions Chapter 10 10.4 Set installation type parameter AS Table 10.4.1 AS parameter values. 10.4.1 Set AS parameter value. NOTICE Installation type. 1. If pull installation is required, set AS = 0. Parameter Parameter description.
ED900 Setup and Troubleshooting Instructions Chapter 10 10.5 Set door width parameter Tb Table 10.5.1 ED900 door widths 10.5.1 Measure door width. and Tb parameter values. 1. Measure door width in inches or mm 10.5.2 Set Tb door width parameter value.
ED900 Setup and Troubleshooting Instructions Chapter 10 10.7 Set door type parameter dL Table 10.7.1 Door type parameter dL values. 10.7.2 Set dL door type parameter value. Door type NOTICE 1. Set dL = 0 (single door =0). Parameter •...
ED900 Setup and Troubleshooting Instructions Chapter 10 10.8 Perform learning cycle Fig. 10.8.1 Mode switch Step 1 Secure motion range of door. Set Mode switch to CLOSE position Step 2 (Fig. 10.8.1). Close Rotating "o" and a "0" indicates operator learning cycle is required.
ED900 Setup and Troubleshooting Instructions Chapter 10 10.9 Set power fail closing speed Fig. 10.9.1 Power fail closing speed potentiometer Power fail closing speed potentiometer Control board 10.9.1 Power fail closing speed Fig. 10.9.2 Power on switch potentiometer. Power on switch •...
ED900 Setup and Troubleshooting Instructions Chapter 11 11 Initial setup – pair doors 11.1 Separately setup active and inactive doors 11.1.1 Setup active door first. 11.1.2 Setup inactive door. 1. Refer to Chapter 10 and setup active door. 1. Refer to Chapter 10 and setup inactive door.
ED900 Setup and Troubleshooting Instructions Chapter 11 11.2.2 Inactive door, set parameter dL. NOTICE 1. Set program switch to CLOSE. Pairs must be: 2. Set parameter dL (door type) for inactive door. • 1 (active) and 2 (inactive) or •...
ED900 Setup and Troubleshooting Instructions Chapter 12 12 Set track bumper stop 12.1 Set track bumper stop position 12.1.1 Set bumper stop position. Fig. 12.1.1 Mode switch 1. Set Mode switch to OPEN. 2. Door moves to set opening angle.
ED900 Setup and Troubleshooting Instructions Chapter 13 13 Install push arm door stop 13.1 Install push arm door stop (optional assembly) Fig. 13.1.1 Door stop assembly HS4633-001 TIPS AND RECOMMENDATIONS 1/2" thick base plate Contact local dormakaba USA, Inc.
ED900 Setup and Troubleshooting Instructions Chapters 14 and 15 14 Check door signage 14.1 Check door signage 14.1.1 Check door signage. TIPS AND RECOMMENDATIONS Check door signage as outlined in ED50LE or ED100LE Low Energy Installation Manual. Reference Chapter 7, ED50LE and ED100LE door signage.
Upgrade cards 16.2 Container module 16.1.1 Upgrade card installation. 16.2.1 Container module dormakaba upgrade cards can be used to expand the range of • The first upgrade card installed becomes functions of ED900 operators. the container module. When upgrade cards are installed, information is exchanged •...
ED900 Setup and Troubleshooting Instructions Chapter 17 17 ANSI/BHMA standards 17.1 Low energy power operated doors (ANSI/BHMA A156.19) The following table references portions of content from ANSI/BHMA A156.19. Refer to the standard, available through ANSI or BHMA for additional information. Standard material reprinted with BHMA permission.
ED900 Setup and Troubleshooting Instructions Appendix A Appendix A - Driving parameters A.1 Driving parameters – detail A.1.1 Driving parameters detail. Value Factory Parameter Units Description range setting Opening speed, automatic mode. 1. Opening speed refers to automatic mode, speed can be adjusted using this parameter.
Page 39
ED900 Setup and Troubleshooting Instructions Appendix A A.1.1 Driving parameters detail. Value Factory Parameter Units Description range setting Safety sensor test. Safety sensor parameter ST must be set to sensors used and if they are active-high or active-low. See E 04 safety sensor test error, Appendix B.
Page 40
ED900 Setup and Troubleshooting Instructions Appendix A A.1.1 Driving parameters detail. Value Factory Parameter Units Description range setting Power reserve module SVP-PR 12 test. Test off 1. SVP-PR 12 power reserve module test is performed once every 24 hours, or 10 minutes after AC power has been turned on.
Page 41
ED900 Setup and Troubleshooting Instructions Appendix A A1.1 Driving parameters detail. Value Factory Parameter Units Description range setting Push & Go. 1. Parameter is activated. 2. Automatic opening of door is started when door is manually moved 4° out of the 0 - 1 closed position.
Page 42
1. Status relay activated when door is opened further than opening angle parameter OA, set during learning cycle. 2. Parameter OA value can only be changed using dormakaba handheld or by performing another learning cycle. Locking device output configuration;...
Page 43
ED900 Setup and Troubleshooting Instructions Appendix A A.1.1 Driving parameters detail. Value Factory Parameter Units Description range setting Factory setting level. Parameter SL is used to determine what data will be reset during factory setting process. Standard factory settings.
Page 44
ED900 Setup and Troubleshooting Instructions Appendix A A.1.1 Driving parameters detail. Value Factory Parameter Units Description range setting Power assist function. 1. Force setting for Power assist function. 2. Power assist function only available with hd parameter = 1, manual mode.
Page 45
COM 1 configuration interface. Interface programmed for communication with dormakaba handheld. 0 - 1 Interface programmed for use with dormakaba TMS Soft control software. Backcheck when door opened manually. 1. Angle after which door is braked when manually opened. 2. Back check level is automatically optimized during manual door opening cycles. This...
Page 46
ED900 Setup and Troubleshooting Instructions Appendix A A.1.1 Driving parameters detail. Value Factory Parameter Units Description range setting Deactivation of drive; X6, 4 and 4a, trigger type. NC contact, drive function is deactivated when NC contact is open. 0 - 1 NO contact, drive function is deactivated when NO contact is closed.
ED900 Setup and Troubleshooting Instructions Appendix B Appendix B - Troubleshooting B.1 Information and error codes Fig. B.1.1 User interface B.1.1 Overview 4 button keypad Operator monitors internal circuits and external safety 2 digit display circuits managed by the operator.
ED900 Setup and Troubleshooting Instructions Appendix B B.1.7 Error message memory. 1. There are ten error message memory locations; E 0 through E 9. 2. The latest error message is always stored in error memory location E 0: •...
ED900 Setup and Troubleshooting Instructions Appendix B B.3 Troubleshooting chart, "ln" codes B.3.1 Troubleshooting chart, information messages. Display Description Troubleshooting information messages Sustained operation on a door with an obstruction can result in damage to drive. 1. Object or person obstructing door movement.
ED900 Setup and Troubleshooting Instructions Appendix B B.3.1 Troubleshooting chart, information messages. Display Description Troubleshooting information messages Communication error, double 1. Check communication cable connection at the two operators. door system. • Cable connects to the horizontal RJ 45 connector next to the user ln 61 •...
Page 51
Display Red LED • Description Troubleshooting error codes EEPROM error. • Internal memory check could 1. Using dormakaba handheld, reload current firmware to not be completed. Flashing E 12 reinitialize system. 12 x • Drive unit works in door closer 2.
Page 52
ED900 Setup and Troubleshooting Instructions Appendix B B.4.1 Troubleshooting chart, "E" codes. Display Red LED • Description Troubleshooting error codes 1. For double door systems, the Upgrade card fire protection must Flashing Incompatible fire protection setting. E 63 double door system.
Page 53
ED900 Setup and Troubleshooting Instructions Blank page This page left intentionally blank. ED900 DL4617-001 09-2021...