Installation

3
Installation
3.1

General Information

Install the module with two M6x25/30 size screws on a level surface. The required torque is
1 Nm. Use washers according to DIN 125. For the installation holes, use a spacing of
237.3 mm to 239.7 mm.
Note
Power supply connection
When connecting the power supply, ensure a separate power supply to the sensor and system
via U
and auxiliary supply via U
s
supply concept for system current and load current, this means the sensor and system area of
the Ethernet IO module can continue working even if there is a failure of the load power supply.
Where several Ethernet IO modules are connected in series, ensure the separate power
supplies are connected properly U
Note
To dissipate interference currents and the EMC resistance, the modules use a short circuit to
ground with an M4 thread. This is marked with the symbol for grounding and the label "XE."
Note
Connect the module using a low-impedance connection with the reference ground. In the case
of a grounded mounting surface, you can connect the module directly via the fixing screws.
Note
For non-grounded mounting surfaces, use a ground strap or a suitable FE conductor. Connect
the ground strap or FE conductor to the grounding point using an M4 screw and place a washer
and a serrated washer under the fixing screw if possible.
Note
Use a suitable UL-certified cable (CYJV or PVVA). To program the controller, please consult the
manufacturer information and use only the appropriate accessories.
Note
For UL application:
Approved only for indoor use. Please observe the maximum altitude of 2000 meters. Approved
up to a maximum of pollution degree 2.
Warning!
Terminals, the housing of field-wired terminal boxes or components may exceed a temperature
of 60 °C.
Warning!
Use temperature-resistant cables with the following properties:
Heat resistant up to at least 96 °C.