10.
H8163 only:
Set the Pulse Rate selection switch to the desired output rate (kWh
per pulse). Note that 0.1 is not valid for 1600A systems, and 0.1 and 0.25 are not
valid for 2400A systems.
11.
Secure the meter cover shut using a padlock, wire tie, or other locking device.
12.
Apply power to the meter.
13.
Check the display. At initial power-up, the meter checks each phase, and, if the
phasing is correct, an OKAY message will appear. If the phasing is incorrect,
an error message will indicate which color leads are not connected properly.
Disconnect power before reconnecting leads.
14.
Check power reading. Expected power is estimated as follows:
kW = Volts(L-L) * Amps * 1.732 * PF 1000
kW = horsepower * 0.746
15.
To reset the kWh accumulator to zero, press and hold the two pushbuttons on the
inside of the meter cover for 10 seconds.
16.
To reset the kW max. register, press and hold the two pushbuttons on the inside
of the meter cover for 5 seconds.
alarms
The following messages remain on the lower display for the duration of an alarm
condition:
Message
Phase loss
The voltage on one phase is less than 75% of the voltage on any other
phase. The displayed message will indicate the problem phase.
Amps Over
The measured current is greater than 110% of the transformer range. The
display message will indicate the problem phase.
Volts Over
Volts A-C, B-C, or A-C is greater than 660VAC.
indicate the problem phase.
The H8163 devices are rated to 300VAC L-N, and the H8150 devices are rated to 132VAC L-N.
Operation above these levels will damage the device.
Z205338-0C
PAGE 8
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Display
Plain
Full
Black
Black
Red
Yellow
Red
Yellow
+ - + - + -
N
A
B
C
N
A
B
C
+ A D + B D
+ C D
Explanation
The displayed message will
©2009 Veris Industries USA 800.354.8556 or +1(0)503.598.4564 / support@veris.com
H81xx
information rePorting
All monitored data is listed below.
kW
Max. kW
PF
Volts
Amps
kVAR
kW, phase A *
kW, phase B *
kW, phase C **
PF, phase A *
PF, phase B *
PF, phase C **
Volts, A-B **
Volts, B-C **
Volts, A-C **
Volts, A-N *
Volts, B-N *
Volts, C-N **
Amps, A *
Amps, B *
Amps, C **
The H81xx continually reports kWh or MWh, depending on the total accumulated
energy. A secondary display cycles through other parameters. The meter has two
modes of display operation, depending on the setting of the Display Data jumper
(J8) on the main circuit board. In Full Display mode, the meter cycles through all
parameters. In Plain Display mode, the meter cycles through only the first five
parameters as listed above.
Every 10th rotation of parameters, the meter displays another set of data elements:
Pulse Rate ***
Address ****
Baud Rate ****
Parity ****
2/4 Wire ****
* For meters with 2 or 3 current transformers.
** For meters with 3 current transformers.
*** H8163 only.
**** H8163, only if a comm board is installed.
INSTALLATION GUIDE