178 076 66-6 P93783 2023-02-07 Providing sustainable energy solutions worldwide Installation- and maintenance instruction B 55-2 FAME/RME LMO24.255C2E E 4N CK Translation of the original instructions.
Page 2
1~230V 1,0A 50Hz IP 20 Motor supply MADE IN SWEDEN BY 1. Manualer på övriga språk 1. Manuals in other languages 1. Manualer på andre sprog 2. www.bentone.com\ 2. www.bentone.com\download 2. www.bentone.com\ nedladdning eller scanna or scan QR-code. download eller scan QR-koden.
Make sure that the burner is suitable for the application (see Technical • Data). All components must be installed without being bent, twisted or • subjected to mechanical or thermal forces that affect components. 165 105 01-2 2021-12-07 Bentone...
Page 5
When in operation, the burner’s noise level can exceed 85 dBA – use • hearing protection! - Operation: Carry out all stipulated settings, service and inspection work within • the set time. • If the oil burner control has a solid red light, contact your installer. Bentone...
Annual cleaning and checking for the presence of water in the tank • should be done to avoid corrosion and microorganisms. 165 405 06 2021-12-07 Bentone...
øC Ø B Ø C 274/374/474 * Min. recommended distance to floor. Burner installation 2.2.1 Hole patten Make sure the hole pattern on the boiler is designed for burner flange. ø (155) 165 ø (226) 254-300 165 205 86-4 Bentone...
Working field 13.0-67.5 kg/h 155-800 kW mbar Do not exceed working field. -1,0 Setting for nozzle assembly and air damper Air settings Nozzle assembly Scale Burner output Bentone...
Nozzle and pump pressure Due to different furnace geometries and capacities, it is not possible to recommend a nozzle model. 45° Solid/semisolid Nozzle: 60° Solid/semisolid 80° Solid/semisolid Pump pressure: 14 bar (14-21 bar) depending on pump model Bentone...
1267 1089 24,00 1254 1078 1297 1116 1341 1153 1382 1188 26,00 1359 1168 1406 1209 1453 1249 1497 1287 The table applies to oil with a viscosity of 4.4 mm /s (cSt) at a density of 830 kg/m Bentone...
Page 11
54,94 56,45 57,92 59,36 12,00 59,93 61,58 63,19 64,76 14,00 69,92 71,84 73,72 75,55 16,00 79,91 82,11 84,25 86,34 1024 The table applies to oil with a viscosity of 4.4 mm /s (cSt) at a density of 830 kg/m Bentone...
The cables of the safety system must be separated so that the outgoing signal is not placed in the same cable as the incoming signal. Wiring diagram Brown Blue Green Yellow Gn/Ye Green/Yellow Black Grey White Orange Violet 165 405 53 Bentone...
< 1 s < 1 s Ambient temperature -5 - +60°C -20 - +60°C Min detector current required (with fl ame) 45 µA dc 45 µA dc Max perm. detector current (without fl ame) 5.5 µA dc 5.5 µA dc Bentone...
If the reset button is instead kept pressed a second time for at least 3 seconds, you can, via an interface, obtain the corresponding information on a computer or flue gas analyser. To return to normal operation: Press the reset button for 1 second. Bentone...
Bleed the oil system. The oil pump/oil preheater may be damaged if • run dry. The vacuum in the suction line should not fall below 0.3 bar during start-up. 165 205 19-3 Bentone...
Electrical connection must be done in accordance with the applicable • regulations. Burners must be connected to an all-pole switch. • • Connection must conform to the wiring diagram. Use appropriately sized fuses. • If any electrical connection is used other than that recommended by Enertech, there may be a risk of damage to property and personal injury. Bentone...
Check oil line seals When the burner has been installed and put into operation, the tightness of Use Loctite 5188 on the various coupling elements should be checked, in case of leakage - tighten threaded oil lines. the coupling elements. 165 105 51-2 2022-03-31 Bentone...
Stage 2 Insert Stage 1 Fuel, Stage 2 Solenoid valve 2 Stage 2 Selection of output and connection between the different power stages must be selected and adjusted so that the system achieves good functionality. 165 205 35-4 Bentone...
Change the oil pump oil fi lter in accordance with the following. • Close the oil valves Unscrew the cover on the pump. • Replace the oil fi lter. • Replace head gasket. • Mount the cover on the pump. • Open the oil valves. • 165 105 86-2 2022-05-17 Bentone...
Vacuum gauge port 5. Inlet Oil under pressure 1. Gear set By passed oil returned to tank, or to suction 2. By-pass hole 6. Pressure adjustment 7. To nozzle 3. Pressure gauge port 4. By-pass plug installed 8. Return Bentone...
Ignition system with fl ame guard 250,000 cycles 10 years UV fl ame sensor 10,000 h Damper motor 500,000 cycles Contactor 500,000 cycles 10 years The burner and its components must be recycled according to applicable regulations. 165 405 07-2 2022-10-04 Bentone...
Install flame tube, be sure to install the drainage hole downwards (not available on all flame tubes) so that any oil spills can drain out. Close boiler/hinged flange. Switch on the main power and open the fuel supply. Start burner and check/adjust combustion. When servicing/replacing components that affect combustion, flue gas analysis and soot test must be carried out following installation. 165 205 36-2 Bentone...
Refit the damper motor. Refit the intake grille. Slide the burner together and secure it with the nuts (E). Switch on the main power and open the fuel supply. Start burner and check/adjust combustion. When servicing/replacing components that affect combustion, flue gas analysis and soot test must be carried out following installation. 165 405 55 Bentone...
Make the electrical connections to the damper motor. message. Reset the damper motor cams. Switch on the main power and open the fuel supply. Start burner and check/adjust combustion. When servicing/replacing components that affect combustion, flue gas analysis and soot test must be carried out following installation. 165 405 56 Bentone...
Replace drive shaft coupling on pump. Refi t coupling, pump and motor, making sure drive shaft is connected correctly at both ends. Switch on the main power and open the fuel supply. When servicing/replacing components that aff ect combustion, fl ue gas analysis and soot test must be carried out following installation. 165 405 77 Bentone...
Fit new oil hoses. Switch on the main power and open the fuel supply. Bleed the pump. Start burner and check/adjust combustion. Use caution when operating the burner, surfaces may be hot. When servicing oil bearing components, check the oil density when the burner is commissioned after servicing. When servicing/replacing components that affect combustion, flue gas analysis and soot test must be carried out following installation. 165 405 57 Bentone...
Disconnect the power supply to solenoid valves Y1, Y2 and Y3. • Provide power to safety solenoid valve Y1S. • Run motor and pump - check that no oil is coming out of the nozzle, • replace solenoid valve if necessary. Use Loctite 5188 on threaded oil pipelines. When servicing/replacing components that affect combustion, flue gas analysis and soot test must be carried out following installation. 165 405 23 Bentone...
Note the connection of the existing component and disassemble. Fit new component with same connection or with specified alternative connection. Switch on the main power and check the operation of the new component. Start burner and check/adjust combustion. When servicing/replacing components that affect combustion, flue gas analysis and soot test must be carried out following installation. 165 105 11-3 Bentone...
• Check tightness of fasteners. Check fan wheel for damage and contamination (replace if necessary). • Check motor shaft and bearings. If they are worn, replace the motor. • Use screw to attach the vibration sensor. 165 405 46 Bentone...
Preheater temperature too low Check preheater function New oil type Adjust the preheater‘s set operating temperature Check that the oil used has the physical parameters that the burner is rated for. If not, change the oil. 165 105 09-2 2021-01-21 Bentone...
Check that the oil used has the physical parameters that the burner is rated for. If not, change the oil. Temperature of the oil from the tank is too low, increase the temperature of oil from tank Clean the pump filter Bentone...
Change the oil or the pump‘s oil parameters Pump worn Replace the pump Pump run using impure oil that has worn the Replace pump and install self-cleaning pump out prematurely filter in the oil system Blocked pump filter Check, clean pump filter Bentone...
Log of flue gas analysis Tel. no: Owner Adresss Tel. no: Installation Boiler Type Make Power kW Burner Type Model Serial no. Fuel Step 1 Step 2 Step 3 Draught in fireplace Fan Press mbar Filter smoke number Flue gas temp. °C Setting brake disc Setting Air damper Pump pressure...
Page 37
EU Declaration of conformity Bentone Oil Burners Type: BF 1 ST 133 B 40 B 65 ST 108 ST 146 B 45 B 70 ST 120 B 30 B 55 B 80 This declaration of conformity is issued under the sole responsibility of the manufacturer.
Page 38
UK Declaration of conformity Bentone Oil Burners Type: BF 1 ST 133 B 40 B 65 ST 108 ST 146 B 45 B 70 ST 120 B 30 B 55 B 80 This declaration of conformity is issued under the sole responsibility of the manufacturer.