Electric Booster Heater Settings; Settings For An Auxiliary Heater With Mixing Valve - Bosch HPC 400 Installation Instructions For Contractors

User interface ems 2
Table of Contents

Advertisement

Service menu
6.2.2
Electric booster heater settings
Settings for an electric booster heater can be made
in
this
menu.
This
menu is only available if an electric booster heater has been set as an
additional heat source
in
the general settings for auxiliary heaters
menu.
The maximum power output of the electric booster heater
is
15
kW.
BOSCH
3'stage
The output for the electric booster heater can be set by the controller to 3 levels between 0 kW and the output of the
I
electric booster heater.
4'stage
The output for the electric booster heater can be set by the controller to 4 levels between 0 kW and the output of the
electric booster heater.
The output for the electric booster heater
is
limited to 1.0
kW.
~----
Reduced 2.0
The output for the electric booster heater
is
limited to 2.0
kW.
[
dd. el.
heaterop.
mode
2
)
Reduced
1.0
Reduced 3.0
The output for the electric booster heater
is limited
to 3.0 kW.
~--------~----------------~--------------~----------------------~
~tep
_ _ _
The output for t
_ h_
e_
el
_
ec
_
tric booster hea
_ t_
e
r_
is
n~t.!!mite_
d
.__
_
_ _
I
Limit comp
o
output
0
...
15 kW
The maximum output of the auxiliary heater
is
limited to the value set here during compressor operation (1.5
12131
j l
,
414.51619112115kW).
Limit
add.
heater output
0
...
15 kW
The maximum output of the auxiliary heater is limited to the value set here if the compressor is not running(1.5 12
I
I
31414.51619
112115
kW).
I
Limit DHW mode output
o
...
15
kW
I
The maximum output of the auxiliary heater for DHW heating is limited to the value set here (1.5 12
13 14
14.5
16
I
9112115 kW). This value
is
always limited by the maximum output of the auxiliary heater with or without the
compressor running set under Limit
add.
heater output and Limit DHW mode output.
·20 ...
20°C
I
If the outside temperature falls below the value set here, the electric booster heater can start operation.
~valence
poin
~
_ _ _
_
___
__
___ _ _
_ _
_ _ _ _
Table 22 Electric additional heater settings
1) Not available
if
Sweden is setas the
country.
2) Only available for liquid/water (L/W) heat pumps and
if
Sweden
is
set
as
the
country.
3) Not available if Germany is set as the
country.
4) Only available
if
Germany is set as the
country.
6.2.3
Settings for an auxiliary heater with mixing valve
Settings for an auxiliary heater with mixing valve can be made in this
menu.
This menu is only available if an auxiliary heater with mixing valve
has been set as an additional heat source in the general settings,for
auxiliary heaters menu.
Menu
item
Adjustment range
description
Mixed
add.
heat.
interface
On/Off
0-10V
Delay time for mixer
0
...
120 min
'--
- -
f---
- - -
l
Mixer runtime
1
...
300
...
6000s
The auxiliary heater with mixing valve can only be switched on or off. The flow temperature
is
controlled by
the mixing
valve.
The auxiliary heater
is
power-controlled by the controller via a 0·10 V signal. Usually, there
is
no mixing
I
I
valve
installed.
1---
Mixing valve startup delayed until auxiliary heater has heated up.
Time for opening or closing the mixing
valve.
Alarm
input
logic
Open contact
1
An open
contact
at the alarm input switches the alarm on.
L __
f-,
C
"..
lo
- s-
e d
-:-
c
- o;...
nt
- a-
c t----~-+-----=.-=.----A
-
cl..;.
os
- e-
d
-
co
- n-
ta
- c-
t a
- t-:
th -e -a
-:-
Ia-rm
- in'-
pu -t-sw
-
i
- tc-h-
e s
- t-:-
he
-
a
-
Ia
- r-
m -o
-n-.
-==-_=._=.-_-
_
- - l
Outs, temp par. mode
I
-20
...
20°C
If
the outside temperature falls below the value set here, the auxiliary heater can start parallel
operation.
Bival. pt. parallel mode
2)
,_
I
I
Outs. temp switch mode
1
r
-
20
...
20 °C
If the outside temperature falls below the value set here, the auxiliary heater can start alternating
operation.
Bival. pt. switch mode
lJ
I
Add. heater DHW cylinder
Yes
An electric booster heater
is installed
in the DHW
cylinder.
r----
-------
No
An electric booster heater
is
not installed in the DHW cylinder.
Table 23 General settings for an auxiliary heater
1) Not available if Germany
is
set as the
country.
2) Only available
if
Germany
is
set as the
country.
16
HPC 400 - 6 720821772 (2017/07)