(6) Read the Pulse Counter Clear Mode Configuration:
Downlink: 063F000000000000000000
Response: 863F010000000000000000 (Current device parameter)
Example for MinTime/MaxTime logic:
Example#1 based on MinTime = 1 Hour, MaxTime= 1 Hour, Reportable Change i.e. BatteryVoltageChange=0.1V
MaxTime
Sleeping(MinTime)
Wakes up and collects data
REPORTS 3.6V
Note: MaxTime=MinTime. Data will only be report according to MaxTime (MinTime) duration regardless BatteryVoltageChange value.
Example#2 based on MinTime = 15 Minutes, MaxTime= 1 Hour, Reportable Change i.e. BatteryVoltageChange= 0.1V.
Sleeping(MinTime)
sleeping
th
0H
15
M
Wakes up and
Wakes up and
collects data
collects data
REPORT 3.6V
3.6V
Does not report
Example#3 based on MinTime = 15 Minutes, MaxTime= 1 Hour, Reportable Change i.e. BatteryVoltageChange= 0.1V.
Wakes up and collects data
sleeping
sleeping
th
0H
15
M
Wakes up and
Wakes up and
collects data
collects data
REPORTS 3.6V
3.6V
Does not report
Notes :
Wakes up and collects data
REPORTS 3.6V
MaxTime
sleeping
th
th
30
M
45
Wakes up and
Wakes up and
collects data
collects data
3.6V
Does not report
Does not report
3.5V |3.5-3.6|=0.1
REPORTS 3.5V
...
th
th
30
M
45
M
Wakes up and
collects data
3.5V
Does not report
MaxTime
Sleeping(MinTime)
sleeping
M
1H
Wakes up and
collects data
3.6V
REPORTS 3.6V
Users push the button,
REPORTS 3.5V.
Recalculate MaxTime.
th
th
1H
1H 10
M
1H 25
Wakes up and
Wakes up and
collects data
collects data
3.5V
3.5V
Does not report
Does not report
8
Wake up and collects data
REPORTS 3.6V
MaxTime
Wakes up and
collects data 3.5V
Does not report
th
M
1H 40
M
1H 55
Wakes up and
collects data
3.5V
Does not report
2H
th
th
M
2H 10
M
Wakes up and
collects data
REPORTS 3.5V