Electrical Wiring - EAS Electric VRV Installation And Owner's Manual

Hide thumbs Also See for VRV:

Advertisement

Available languages

Available languages

3. Please use attached heat-insulating materials do the heat
insulation without clearance for the connecting parts of the
indoor unit pipes.
The unit body
Affiliated heat pump belt
5.12 Refrigerant Amount to be Added
Calculate the added refrigerant according to the diameter and
the length of the liquid side pipe of the outdoor unit/indoor unit
connection. Calculate the refrigerant adding amount, adding
refrigerant R410A.
Liquid Side Piping
Diameter
Φ6.4
Φ9.5
Φ12.7
Φ15.9
NOTE: R410A refrigerant should be added in liquid quantifiedly by
electronic scale.
5-13 Manifold installation key points
Install it in a horizonal level, error angle should less than 10°.
It may result in damage if installing in a wrong way

6. ELECTRICAL WIRING

CAUTION
Please select power source for indoor unit and outdoor unit
respectively.
The power supply has specified branch circuit with leakage
protector and manual switch.
The outdoor unit model which corresponding to different outdoor
unit power supply should refer to the nameplate.(Please set all
the indoor unit power of one system into the same branch circuit.)
Please put the connective wire system between indoor unit and
outdoor unit with the refrigerant system together.
Use 3-core shielded wire as indoor unit and outdoor unit signal
wire.
The installation should comply with local electric standard.
Power wiring should be engaged by specialized electrician.
Cut from upward
Site pipe side
Fig.5-13
Table 5-13
Refrigerant to be Added
Permeter Piping
0.022kg
0.057kg
0.110kg
0.170kg
Fig.5-14
6.1 Outdoor unit wiring terminal instructions
K1 K2 E O A E
Outdoor unit
central monitor
NOTE:Use 3-core shielded wire to ground wiring
A
380-415V 3N ~ 50Hz
NOTE: Outdoor unit central monitor, digital electric meter, indoor unit
central monitor are all optional components in the dotted box,
if necessary, please contact to the local dealer to buy those.
6.2 Indoor unit system wiring
1. Individual power supply (without power supply device)
(See the table below)
Thinnest electric wire diameter(mm
Item
(Metal tube synthetic resin wiring)
Power
Source
Under
20m
Model
380-415V
33.5kW
4×6mm
3N~ 50Hz
40kW
380-415V
4×10mm
45kW
3N~ 50Hz
Wiring diameters and continuous lengths in the table are the
situation that voltage decrease degree is within 2%, when the
wiring continuous length exceeds the values in the table, choose
the wire diameter according to regulations
12
X Y E
P Q E
Digital
Indoor unit
Indoor unit
electric meter
central monitor
central monitor
B
C
N
XT2
2
)
Hand switch
Under
Ground
Breaker Fuse
50m
wire
2
2
2
4×10mm
6mm
40
2
2
2
10mm
4×16mm
50
CAUTION
Fig.6-1
Fig.6-2
Table 6-1
Leakage
protector
Under 100mA
40
0.1 sec
Under 100mA
50
0.1 sec
V.2