14. Locate the shower unit on the inlet
supplies and push the inlet manifold
onto the pipework until resistance is
felt.
DO NOT FORCE!
Note! PTFE tape or liquid jointing
compound must not be used and is
not required to assist connection.
15. The inlet manifold collet and 'O'
seals will seal automatically.
Warning! The shower unit must
be fixed to the wall at all three
fixing points. The fixing holes are
elongated to assist in vertical and
horizontal alignment.
16. Screw the shower unit to the wall
using either the wall screws supplied
or alternative fixings depending on
the wall structure.
Do not over tighten!
Make sure that the electrical supply
cable is correctly seated in the
channel in the back of the case.
17. Connect the live, neutral and earth
conductors of the electrical supply
cable to the terminal block in the
following manner.
L - Live terminal block
N - Neutral terminal block
- Earth terminal block
The earth supply cable must be
sleeved and make sure that all the
terminal connections are tight and
that no insulation is pinched.
18. Make sure the flow control gear is
set to the OFF position by turning
the gear wheel anticlockwise until it
stops. DO NOT force the gear wheel
as damage will occur.