CAST XFP 16 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL

TECHNICAL SPECIFICATION

POWER SUPPLY
Mains supply (a.c.)
Internal power supply
Maximum rated current
Current specification
Maximum internal battery resistance
Earth fault monitoring
Mains supply & battery charger monitored for failure
Batteries monitored for disconnection & failure
Batteries protected against deep discharge
Maximum battery size and type
Quiescent current
LOOP DRIVER (PROGRAMMABLE & MONITORED)
Number of loop drivers
Communication protocol
Loop monitored for open and short circuit faults
On-board loop isolators
Auto-polling from each loop end & both ends (A & B) Yes
Maximum output current & voltage per loop
Max. number of addressable devices (detectors, MCPs) 255 CAST devices per loop
Device addressing options
Short-circuit isolator in every loop device
Maximum loop cable length
Number of programmable sounder groups
Number of programmable output sets
CONVENTIONAL SOUNDER CIRCUIT (PROGRAMMABLE & MONITORED)
Number of sounder circuits
End of line (EOL) resistor value
Line monitored for open and short circuit faults
Each output fused at (max. sounder output current)
Output voltage
Maximum line length per circuit
AUXILIARY OUTPUTS (PROGRAMMABLE)
Relay type / Output
3 x auxiliary relays (Relay1, Relay2, Relay3)
1 x failsafe fault relay
'+24Vd.c.' Aux. power output
AUXILIARY INPUTS (PROGRAMMABLE, NON-MONITORED)
2 x auxiliary inputs (I/P1, I/P2)
FUSES
(to EN60127-2)
Primary fuse (F1)
Battery fuse (F2)
CONTROLS AND INDICATORS
Control buttons
Event scrolling and menu access buttons
Liquid crystal display
Number of zonal LED indicators
Other LED indicators
PHYSICAL
Dimensions
Weight / Construction
IP Rating (to EN60529)
Paint finish
CABLING REQUIREMENTS
Type of cable
Maximum loop cable length
Connector blocks
Maximum allowable loop impedance (each conductor) 20 ohm
Maximum cable capacitance
NETWORK (OPTIONAL)
Network connection
Network type
Maximum number of main panels per network
Maximum no. of repeaters per non-networked main panel 8
Maximum cable length per network
PC/PRINTER INTERFACE
PC connection
Printer connection
OPERATING CONDITIONS
The enclosure is designed for indoor use only. The components are selected to operate within their specification when the environmental conditions
outside the enclosure comply with class 3k5 of IEC 721-3-3. Temperature range: -10
CERTIFICATES
(Certificates and DOPs are available for download on C-TEC's website)
LPCB Certificate Number: 176b
Declaration of Performance: DOP0000071
ENGINEERING MANUAL • Approved Document No. DFU5010000 Rev 4 • Page 47 of 48
CAST XFP 1 Loop 16 Zone Panel (Part No. XFP501E/CA)
230V ∿ 50/60Hz. Rated current 0.35A r.m.s.
18.7Vd.c. to 29.0Vd.c. (Ripple voltage 500mV p-p)
1.5A @ 230Va.c. (1.5A battery only with Mains off)
I max. a = 300mA; I max. b = 1.1A; I min. = 100mA
Ri max. = 1.1Ω
Yes (any conductor)
Yes
Yes
Yes
2 x 12V, 0.8Ah to 3.2Ah VRLA batteries. Use YUCEL Y3.2-12 for LPCB approved systems.
50mA (with Mains off)
1
CAST® (C-TEC Addressable System Technology)
Yes
Yes
500mA (Voltage: 40V)
Devices automatically addressed by the panel, or manually addressed using CAPROG
Yes
1km
16
16
2 (programmable, independent conventional circuits)
6800 ohm, 5% tolerance, 0.25W
Yes
400mA. Protected by resettable overload circuit.
19.5V minimum; 28V maximum
500m
Volt-free, single pole changeover / 1A, 30Vd.c. (maximum)
Programmed from cause and effects
Active when no faults are present
19.5V minimum, 28V maximum. Maximum current 100mA.
Connect to 0V to trigger, maximum input voltage 27Vd.c. (non-latching).
T 1A H 250V 20mm ceramic
(T=Time Delay, H=High Breaking Current)
1.6A F 20mm ceramic
(F=Fast Acting)
Menu, More Information, Silence Internal Sounder, Control Panel Reset, Investigate,
Silence/Resound Sounders
(scroll up) 5 (1),
(scroll down) 6 (3),
Two lines x 40 characters, backlit
16
(General) Fire, Supply Present, Test, Accessed, General Disablement, Phased Evacuation,
General Fault, Power Supply Fault, System Fault, Sounder Status, Delays Running.
380mm(W) x 235mm(H) x 90mm(D)
1.8kg (without batteries) / plastic detachable lid & plastic back box
IP30
Light grey texture (RAL7035) epoxy paint
Fire resistant screened cable, minimum size 1mm
1km
Fixed type, largest acceptable conductor size, 1.5mm
.27µF
Via XFP761 network driver card, one card fitted at each networked main panel
2-wire, screened, enhanced fire-resistant cable ≥1 mm
8
1km (main panel network); 500m (repeater panel network)
Via main PCB RS232 molex connector (lead supplied with XFP507 PC programming tools)
Not available
o
C to +40
LPCB Reference Number: 176b/26
Tested to: EN54-2:1997 + A1:2006 and EN54-4:1997 + A1:2002 + A2:2006
Accept 4 (2),
Escape 3 (4)
2
2
2
, RS485 non-redundant network
o
C. Maximum humidity: 95% non condensing.
CPR Certificate Number: 2831-CPR-F2522