CAST XFP 16 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
Option 2: Select 'Erase Loop 1 device data first? Yes'
CAUTION: USING THIS OPTION WILL COMPLETELY ERASE THE PANEL'S DATABASE OF
STORED LOOP DEVICE INFORMATION EXCLUDING DEVICE ADDRESSES PREVIOUSLY
ASSIGNED BY A CAPROG PROGRAMMER, WHICH IS RETAINED. THIS IS DIFFERENT TO THE
AUTO ADDRESS FUNCTION. USE THIS OPTION WITH EXTREME CARE.
Use this option if the panel has not previously been programmed, or if you want to program an existing
system as if it were a new system.
5
Press the scroll
button to select 'Yes' then press the Accept
Erase loop 1 device data first? Yes
The following two options will now be available:
Are you sure you want to erase
the Database? No
To select 'No', press the Accept
Only if you are confident to proceed, press the scroll
4
Accept
button. The panel will erase its database, update its flash memory and start a loop learn. Wait
for the process to complete and a summary window will appear, similar to the one shown below:
112 Devices Found
Auto learn complete, Press Accept
4
Press the Accept
button then press Escape
When requested by the panel remove the NVM link shown below:
AFTER A SUCCESSFUL LOOP LEARN, YOU WILL HAVE A 'ONE OUT, ALL OUT' FIRE ALARM SYSTEM.
See Table 1 below for the default device assignment following a loop learn.
DEVICE
Loop Smoke/Heat/Multi-Detectors
Loop Manual Call Points
Loop I/O Unit Inputs
Loop I/O Unit Outputs
Loop Sounders/VADs
Panel Conv. Sounder Circuit 1
Panel Conv. Sounder Circuit 2
Assignment Terms:
Input devices such as detectors, manual call points and the input channels of I/O units are programmed
to be members of a Zone.
Output devices such as loop powered sounders, sounder control units and the panel's conventional
sounder circuits are programmed to be members of a Group.
The output channels of I/O units and the panel's relays are programmed to be members of a Set.
Default Cause & Effects (C&E): Zone 1 triggers Group 1 and Set 1.
Classifying input and output devices in this manner greatly simplifies cause & effects programming.
ENGINEERING MANUAL • Approved Document No. DFU5010000 Rev 4 • Page 23 of 48
4
button, the panel will start a loop learn without erasing the database.
3
button x 3 to return the panel to a normal condition.
DEFAULT ASSIGNMENT
Zone 1
Zone 1
Zone 1
Set 1
Group 1
Group 1
Group 2
4
button shown below:
Are you sure you want to erase
the Database? Yes
5
button to select 'Yes', then press the
Table 1 : Default Device Assignment