C-TEC CAST XFP Engineering Manual page 17

Networkable analogue addressable fire alarm control panel
Table of Contents

Advertisement

CAST XFP 16 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
Fig.13 : CAST XFP Menu Structure
AL1
ENTER ACCESS LEVEL 2
ENTER ACCESS LEVEL 3
DISPLAY FIRE EVENTS *
DISPLAY FAULT EVENTS *
DISPLAY DISABLEMENTS *
DISPLAY ZONES IN TEST *
LAMP TEST
DISPLAY ALARM COUNTER
AL2 CODE
ENTRY
AL2
ENTER ACCESS LEVEL 3
DISPLAY FIRE EVENTS *
DISPLAY FAULT EVENTS *
DISPLAY DISABLEMENTS *
DISPLAY ZONES IN TEST *
LAMP TEST
DISPLAY ALARM COUNTER
SET TIME/DATE
EVENT LOG FUNCTIONS
SET/CLEAR DISABLEMENTS
CHANGE ACCESS LEVEL 2 CODE
AL3 CODE
ENTRY
AL3
DISPLAY FIRE EVENTS *
DISPLAY FAULT EVENTS *
DISPLAY DISABLEMENTS *
DISPLAY ZONES IN TEST *
SETUP PASSWORDS
CONNECT TO PC
NETWORK FUNCTIONS
COMMISSIONING FUNCTIONS
ENGINEER FUNCTIONS
MENU NAVIGATION
PRESS ACCEPT
BUTTON TO MOVE FORWARD.
PRESS ESCAPE
BUTTON TO MOVE BACK.
PRESS SCROLL
BUTTON TO MOVE UP.
PRESS SCROLL
BUTTON TO MOVE DOWN.
ENGINEERING MANUAL • Approved Document No. DFU5010000 Rev 4 • Page 17 of 48
MENU BUTTON
AL2 K/S
ENTRY
AL1 - ACCESS LEVEL 1
AL2 - ACCESS LEVEL 2 (Code 3333)
AL3 - ACCESS LEVEL 3 (Code 4444)
* THE MENU OPTION SHOWN WILL ONLY BE
AVAILABLE IF RELEVANT TO THE PANEL'S STATUS.
Total Alarms = nnn
Alarms Since nn/nn/nn = n
KEYSWITCH (K/S)
Total Alarms = nnn
Alarms Since nn/nn/nn = nn
PRINT EVENT HISTORY
DISPLAY EVENT HISTORY
RESET EVENT HISTORY
ENABLE/DISABLE ZONES
ENABLE/DISABLE SOUNDERS
ENABLE/DISABLE OUTPUTS
ENABLE/DISABLE RELAYS
ENABLE/DISABLE DEVICES
ENABLE/DISABLE FAULT RELAY
ENABLE/DISABLE OUTPUT DELAYS
CHANGE ACCESS LEVEL 2 CODE
CHANGE ACCESS LEVEL 3 CODE
SET COMMS FUNCTION
SET PANEL NUMBER
SET PANEL FITTED
LOOP LEARN
ADDRESS FUNCTIONS
SHOW FITTED DEVICES
ASSIGN ZONE/GROUP
SET DAY/NIGHT TIMES
ENABLE/DISABLE DST ADJUSTMENT
CONFIGURE SOUNDER DISABLEMENTS
SWAPPED DEVICE DETECTION
CONFIGURE POLLING LED
MAKE A CLEAN START
RESTART THE LOOP
SET/CLEAR DISABLEMENTS
MONITOR A POINT
TEST DEVICE OUTPUTS
TEST OUTPUT SETS
TEST SOUNDERS IN GROUPS
TEST VADS IN GROUPS
TEST PANEL RELAYS
WALK TEST
IDENTIFY LOOP BREAK
LOOP TEST
DISPLAY DATABASE
VERSION NUMBERS
SHOW PSU STATS
ENABLE/DISABLE EARTH FAULT
SHOW DEVICE EEPROM
TURN LEDS ON/OFF
DIAGNOSTIC FUNCTIONS
Clear to todays date?
Alarms Since nn/nn/nn = nn
AUTO ADDRESS
REPLACE/ADD DEVICE
CHANGE ADDRESS
SHOW DUPLICATE ADDRESSES
FIX DUPLICATE ADDRESSES
IDENTIFY LOOP CHANGES
ENABLE/DISABLE ZONES
ENABLE/DISABLE SOUNDERS
ENABLE/DISABLE OUTPUTS
ENABLE/DISABLE RELAYS
ENABLE/DISABLE DEVICES
ENABLE/DISABLE FAULT RELAY
ENABLE/DISABLE OUTPUT DELAYS

Advertisement

Table of Contents
loading

This manual is also suitable for:

Xfp501e/ca

Table of Contents