C-TEC CAST XFP Engineering Manual page 27

Networkable analogue addressable fire alarm control panel
Table of Contents

Advertisement

CAST XFP 16 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
CHANGE ADDRESS
This function is used to change device addresses at the panel, therefore saving the use of ladders to
access a device on site.
Note: The CAPROG Handheld Programmer can be used to manually change the address of a device, but
this will also require a loop learn to be carried out.
Enter AL3 (4444) > Commissioning Functions > Address Functions > Change Address.
When the CHANGE ADDRESS prompt is displayed press the Accept
displayed:
Old Address: 1
Enter the address you want to change using the
The device's LED will light and the following is displayed, for example 'Device 8'.
Loop : 1 Device : 8
New Address : 8
Enter the new address of the device using the
4
the Accept
button.
Loop : 1 Device : 8
New Address : 9
In this example the panel will auto-assign address 8 to address 9.
When requested by the panel fit the NVM link shown below:
Please fit the NVM Link now
Wait until the old address is flashing, address 8 is shown below.
Old Address: '8'
3
Press Escape
button x 4. The panel will re-learn and a brief summary window will appear, similar to
the one shown below:
112 Devices Found
Auto learn complete, Press Accept
4
Press the Accept
button then press Escape
When requested by the panel remove the NVM link shown below:
ENGINEERING MANUAL • Approved Document No. DFU5010000 Rev 4 • Page 27 of 48
5
6
and
scroll buttons then press the Accept
5
6
and
scroll buttons, for example 'Device 9', then press
button to return the panel to a normal condition.
3
4
button and the following is
4
button.