CAST XFP 16 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
TEST VADS IN GROUPS
This function allows you to test one, or all of the system's VADs groups by altering their state from
Normal to Triggered.
Enter AL3 (4444) > Engineer Functions > Test VADS in Groups.
When the TEST VADS IN GROUPS prompt appears, press the Accept
window will appear:
VAD Group : 1
5
6
Press the
and
scroll buttons to select the sounder group you would like to test (1 to 16). Press the
4
Accept
button and the following window will appear:
VAD Group : 1 is Normal
Change the state using the Accept button
4
Press the Accept
button to change the state of the selected VAD group between Normal and
Triggered, shown below:
VAD Group : 1 is Triggered
Change the state using the Accept button
Should you want to test additional VAD groups, press the
the VAD group's number and state.
TEST PANEL RELAYS
This function allows you to test the panel's three volt-free relays.
Enter AL3 (4444) > Engineer Functions > Test Panel Relays.
When the TEST PANEL RELAYS prompt appears, press the Accept
window will appear:
Panel Relay : 1
5
6
Press the
and
scroll buttons to select the relay you would like to test (1 to 3). Press the
4
Accept
button and the following window will appear.
Panel Relay : 1 is Normal
Change the state using the Accept button
4
Press the Accept
button and the panel relay you have selected will trigger. To change the state back
to Normal press the Accept
ENGINEERING MANUAL • Approved Document No. DFU5010000 Rev 4 • Page 40 of 48
4
button again.
4
button and the group selection
5
6
and
and Accept
4
button and the panel relay selection
Panel Relay : 1 is Triggered
Change the state using the Accept button
4
buttons to change