C-TEC CAST XFP Engineering Manual page 25

Networkable analogue addressable fire alarm control panel
Table of Contents

Advertisement

CAST XFP 16 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
When requested by the panel remove the NVM link shown below:
AFTER A SUCCESSFUL AUTO ADDRESS, YOU WILL HAVE A 'ONE OUT, ALL OUT' FIRE ALARM
SYSTEM. See Table 1 page 23 for the default device assignment following an auto address.
Option 2: Select 'Continue from last address? Yes'
Use this option if you do not want to erase the stored loop device data. The panel will start to learn
the loop from the last known address in its memory. Existing data will not be overwritten, e.g.
zone and group allocation, device names, etc., will remain unchanged. The only data that will be
overwritten is device type and whether or not it is fitted.
5
Press the scroll
button to select 'Yes' then press the Accept
Continue from last address? Yes
The panel will perform an auto address. Wait for the process to complete and a brief summary
window will appear, similar to the one shown below:
112 Devices Found
Auto learn complete, Press Accept
4
Press the Accept
button then press Escape
When requested by the panel remove the NVM link shown below:
ENGINEERING MANUAL • Approved Document No. DFU5010000 Rev 4 • Page 25 of 48
4
button shown below:
3
button x 4 to return the panel to a normal condition.