CAST XFP 16 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
ENABLE/DISABLE DEVICES
This function allows loop devices to be disabled from reporting faults, fires, etc., and is normally used
to temporarily disable detectors/call points that are nuisance tripping.
Enter AL3 (4444) > Engineer Functions > Set/Clear Disablements > Enable/Disable Devices.
When selected, press the Accept
Loop : 1
5
6
Press the
and
scroll buttons and Accept
selected, the following display will appear, for example:
Loop : 1
From : 1 to 5
Enabled
5
6
Press the
and
scroll buttons to toggle between enabled and disabled, then press the Accept
to select.
Note: If all input devices on a zone have been disabled, the zone they belong to will also be disabled.
If you try to re-enable a zone which has no enabled devices on it using the ENABLE/DISABLE ZONES
function described on page 34, a prompt appears saying this cannot be done. Instead you MUST enable
at least one device on the zone before re-enabling the zone itself.
ENABLE/DISABLE FAULT RELAY
This function can be used to suppress the panel's single, fault relay output from activating in a fault
condition.
Enter AL3 (4444) > Engineer Functions > Set/Clear Disablements > Enable/Disable Fault Relay.
When selected, press the Accept
Fault Relay output is :
Enabled
5
6
Press the
and
scroll buttons to toggle between enabled and disabled and press the Accept
to select the desired option. Alternatively, to return to the previous menu press the Escape
ENABLE/DISABLE OUTPUT DELAYS
This function can be used to globally enable (TURN ON) or disable (TURN OFF) any delays to outputs
that have been programmed by an engineer.
Enter AL3 (4444) > Engineer Functions > Set/Clear Disablements > Enable/Disable Output Delays.
When selected, press the Accept
Delays to Outputs are :
Enabled
5
6
Press the
and
scroll buttons to toggle between enabled and disabled and press the Accept
to select the desired option. Alternatively, to return to the previous menu press the Escape
ENGINEERING MANUAL • Approved Document No. DFU5010000 Rev 4 • Page 36 of 48
4
button and a window similar to the one below will appear:
4
buttons to select the loop and range of devices. When
4
button and the following window will appear:
4
button and the following will appear:
4
button
4
button
3
button.
4
button
3
button.