LPCB APPROVED CFP ALARMSENSE 2/4/8 ZONE FIRE ALARM PANEL

TECHNICAL SPECIFICATION

POWER SUPPLY SPECIFICATION
Mains supply voltage (a.c.)
Mains rated current
Internal power supply
Maximum rated current
Current specification
Maximum internal battery resistance
Supply and battery charger monitored for failure
Batteries monitored for disconnection & failure
Batteries protected against deep discharge
Maximum battery size and type
Mains fuse (F1) compliant with IEC/EN60127-2
Battery fuse (F2) compliant with IEC/EN60127-2
Current draw from battery (Mains failed)
ZONE CIRCUIT SPECIFICATION (for use with AlarmSense
Number of circuits
Maximum cable length per circuit
Line monitored for head out, open & short circuit
Line monitored for detector removal
Maximum allowable impedance (each conductor)
Maximum cable capacitance (per circuit)
Maximum number of detectors & manual call points
Maximum number of sounders per zone
AlarmSense
optical & heat detector specification
AlarmSense
manual call point specification
AlarmSense™ sounder specification
Note: Sounder current limited to 200mA per zone
CONVENTIONAL SOUNDER CIRCUIT SPECIFICATION (for use with non-AlarmSense
Number of circuits
End-of-line (EOL) resistor value
Each circuit monitored for open and short circuit
Alarm voltage
Sounder circuit fuses
Maximum total sounder output current to all outputs 4 x 200mA = 800mA
Maximum No. of bells @ 25 mA
Maximum No. of electronic sounders @ 20 mA
AUXILIARY OUTPUTS (Open Collector Type)
Reset auxiliary output (RESET)
Remote auxiliary output (REM)
Maximum sink current
Maximum open circuit voltage
24V aux. power output (for use with the above)
AUXILIARY OUTPUTS (Relay Output Type)
Auxiliary relay output (AUX)
Fault relay output (FAULT)
Maximum switching current
Maximum switching voltage
AUXILIARY INPUTS
Class Change (makes sounders sound continuously)
Alert (makes sounders pulse intermittently)
PHYSICAL
Product dimensions
Hole required for flush mounting
Weight
IP rating (to EN 60529)
Construction & Finish
OPERATING CONDITIONS
The components are selected to operate within their specification when the environmental conditions outside the enclosure
comply with class 3k5 of IEC 721-3-3. Temperature range: -10
CERTIFICATES
(Certificates and DOPs are available for download on C-TEC's website)
LPCB Certificate Number: 176b
Tested to: EN 54-2:1997 + A1:2006 & EN 54-4:1997 + A1:2002 + A2:2006
INSTALLATION & MAINTENANCE MANUAL • Approved Document No. DFU7002020 Rev 4 • Page 24 of 24
CFP702-2 (2 Zone), CFP704-2 (4 Zone), CFP708-2 (8 Zone)
230V
0.35A r.m.s.
27Vdc nominal (Ripple voltage 500mV)
1.5A @ 230Vac
I max. a = 146mA, I max. b = 1A, I min. = 25mA
Ri max. = 1.5Ω
YES (battery charger is also temperature compensated)
YES
YES (Deep discharge cut off approx. 21 volts)
2 x 12V 3.2Ah VRLA type, connected in series. Use YUCEL Y3.2-12 for
LPCB approved systems. Minimum battery size 1.2Ah.
T 1A H 230V, 20mm ceramic (T = Time Delay; H = High Breaking Capacity)
F 1.6A, 20mm ceramic (F = Fast)
1.5A maximum
2, 4 or 8 (1 zone per circuit) depending on model purchased
500 metres
YES - DC monitoring
YES. End-of-line monitoring device modules provided.
20Ω
0.27
25 per zone
See Sounder Loading section on page 8
Quiescent current <50
Quiescent current <50
Quiescent current <20µA; Alarm current 4-16mA depending on tone and
volume. Sounders operate when zone voltage is above 20V.
4
6800Ω 5% Tolerance 0.25W (blue, grey, red, gold)
YES - Reverse voltage DC monitoring. Indicated by common fault.
27VDC maximum, 20VDC minimum (final battery voltage)
Each circuit protected by fuses (200mA min. hold current; 400mA maximum
trip current; approx. 50mA when tripped. Reset when faults removed).
32
40 (sounders must be polarised)
Non monitored, open collector type. Active during reset cycle.
Non monitored, open collector type. Active during any fire condition
(provided all relevant delays have expired).
30mA each
27Vdc
This output is protected by a resettable fuse (100mA min. hold current).
Fuse resets when fault removed.
Voltage-free single pole changeover
Voltage-free single pole changeover
1A
30Vdc
Connect to 0V to trigger. Maximum input voltage 27V (non-latching).
Connect to 0V to trigger. Maximum input voltage 27V (non-latching).
380 (W) x 235 (H) x 96 (D) mm
367 (W) x 220 (H) x 75 (D) mm. No bezel required.
1.75kg (without batteries)
IP30
Plastic lid and base; RAL7035 textured
LPCB Reference Numbers: CFP702-2 (176b/14); CFP704-2 (176b/15); CFP708-2 (176b/16)
∿,
50/60Hz
devices only)
µ
F
µ
A; triggered voltage 9V nominal
µ
A; triggered voltage 5V nominal
o
C to +40
o
C. Maximum relative humidity: 95% non condensing.
CPR Certificate Number: 2831-CPR-F0386
sounders)
DOP No. DOP0000037