Controls And Indicators - C-TEC CAST XFP Engineering Manual

Networkable analogue addressable fire alarm control panel
Table of Contents

Advertisement

CAST XFP 16 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL

CONTROLS AND INDICATORS

Front panel layout
Fire Alarm Control Panel Instructions
To view more events use the scroll
To silence the internal sounder: press
To silence/resound the alarm sounders:
Turn key to l and press
OR press
and
. Enter code and press
To reset the panel:
Ensure all alarm conditions are silenced and
investigations are complete and press
To exit access mode:
Remove key OR press and hold
General fault
flashing light - call engineer
XFP
LED Indicators
Liquid Crystal Display
(General) Fire
Fire Zones (1-16)
Supply Present
Test
Accessed
General Disablement
Phased Evacuation
General Fault
Power Supply Fault
System Fault
Sounder Status
Delays Running
ENGINEERING MANUAL • Approved Document No. DFU5010000 Rev 4 • Page 14 of 48
buttons
escape
CA ST XFP SERIES
The system must be
tested regularly.
If in doubt, refer to
the user manual.
176b
EN54-2 & EN54-4
Manufactured in England
Provides detailed information on the status of the system (the type of messages
displayed and what they mean is covered in greater detail in the panel's
separate user manual).
Flashes red when there is a fire condition on any zone and goes steady red
when the alarm is silenced. Subsequent fire conditions will restart the (General)
Fire indicator flashing until it is silenced again.
One or more of these indicators will flash red in an alarm condition and will go
steady when silenced.
Normally lit green to show that all of the panel's power supplies are
functioning correctly.
Lit yellow when the panel is in walk test mode. This LED does NOT illuminate
for any other test condition.
Lit yellow when the panel is in access levels 2 or 3.
Lit yellow when one or more zone, sounder, output or relay is disabled.
Flashes yellow when there is a phased evacuation in progress.
Flashes yellow when there is a fault condition on the panel. Will always be lit
in conjunction with at least one other fault LED.
Lit yellow when the panel's power supply or Mains has failed or the panel's
standby battery is in poor condition.
Lit amber when a system error, such as a microprocessor fault, occurs AND REMAINS
LIT EVEN IF THE SYSTEM FAULT CLEARS. THIS SYSTEM FAULT LED CAN ONLY BE
CLEARED BY PRESSING THE CONTROL PANEL RESET BUTTON AT AL2 OR AL3.
Flashes yellow when a fault is detected on either of the panel's two
conventional sounder circuits or if there is a sounder disablement anywhere on
the system.
Lit yellow when one or more output delays has been programmed by an engineer.
Flashes yellow when one or more output delays are running.
10:59:03 24 Jun
: Normal
FOXCO WAREHOUSING
Fire
more
information
1
accept
9
silence internal
menu
sounder
supply
present
control panel
silence/resound
reset
sounders
general
investigate
fault
Fire Zones
3
5
6
2
4
11
13
14
10
12
general
test
accessed
disablement
power
system
sounder
supply
fault
status
fault
8
7
16
15
phased
evacuation
delays
running