CAST XFP 16 ZONE ANALOGUE ADDRESSABLE FIRE ALARM PANEL
Press the Menu button and the following is typically displayed:
Between Devices 7 & 8
Ground floor: Loop:1 Device 7
Fix the loop break at the location identified.
Press the Control Panel Reset button then press Escape
The panel returns to normal if the loop break is fixed.
To identify a short circuit
The following fault may have been displayed at the panel.
S/C Detected
Loop 1
Enter AL3 (4444) > Engineer Functions > Identify Loop Break.
When the IDENTIFY LOOP BREAK prompt appears, press the Accept
initialize both ends of the loop and the following is displayed:
Restarting Loop...
Please Wait
The following is displayed:
Loop Integrity Fault
On Loop 1
The LEDs on the devices either side of the short circuit will light steady red.
Press the Menu button and the following is typically displayed:
Between Devices 7 & 8
Ground floor: Loop:1 Device 7
Fix the short circuit in the loop at the location identified.
Press the Control Panel Reset button then press Escape
The panel returns to normal if the loop short circuit is fixed.
ENGINEERING MANUAL • Approved Document No. DFU5010000 Rev 4 • Page 42 of 48
3
button x 3.
4
button and the panel will
3
button x 3.