WARNING
To guarantee safety and correct operation of the system
interface, it must be commissioned by a qualifi ed techni-
cian in possession of the skills as required by law.
IGNITION PROCEDURE
- Insert the system interface into the connection shoe by
pushing it gently downwards; after a brief initialisation,
the system interface will be connected.
- The display screen shows "Select language". Turn the
knob and select the desired language. Press the OK but-
ton to confi rm.
- The display shows date and time.
Use the knob to select the date, press the OK button, turn
the knob to select the exact day, press the OK button to
confi rm and move on to the month, followed by the year,
pressing the OK button to confi rm after each step. Turn
the knob to select the time, press the OK button, turn the
knob to select the exact hour, press the OK button to
confi rm and move on to the minute value. Press the OK
button to confi rm. Turn the knob and select summer time,
press the OK button, select auto or manual, press the OK
button.
The display shows the basic screen.
- Select the country
Now follow step by step directions that appear from time
to time on the display.
TECHNICAL AREA ACCESS
- Simultaneously press the back "
til "Insert code" appears on the display.
- Turn the knob to enter the technical code (234) then
press OK; the display will show TECHNICAL AREA:
- Language, date and time
- BridgeNet Bus network settings
- Complete menu
- Confi guration Wizard
- Service
- Faults
Turn the knob and select:
- BridgeNet Bus network settings
The display will show the list of devices connected within
the system:
- System interface (local)
- Energy Manager
- Zone Manager
To set the correct zone to which the system interface is
associated, turn the knob and select:
- System interface (local)
Press the OK button. Turn the knob and set the correct
zone. Press OK to confi rm the setting.
Turn the knob and select:
- COMPLETE MENU
Press the OK button to confi rm. Turn the knob and select:
17.0
User parameters
17.0.0 CH mode
- Green
(excludes the electric resistances for the integration of
the heating)
- Standard
Press the OK button to confi rm.
17.0.1
Quiet Mode Activation
Press the OK button to confi rm.
"and "OK" buttons un-
Turn the knob and select:
- ON (active function to reduce noise)
- OFF
Press the OK button to confi rm. Turn the knob and select:
17.0.4 Domestic Hot Water BOOST
Press the OK button to confi rm.
Turn the knob and select:
- ON (enable the boost cycle to speed up the DHW servi-
ce. Max duration 180 min.)
- OFF
17.0.5 Delta T PV sanitary setpoint
Turn the knob to set the value that encreases the
sanitary setpoint when the PV contact is supplied.
17.1
EM INPUT OUTPUT CONFIGURATION
Press the OK button to confi rm. Turn the knob and select:
17.1.0
HV Input 1
- Not defi ned: no function associated to the input. Fault
941 is displayed.
- Absent: Input not enabled.
- EDF (night tariff ): Input not active (0V). If the Comfort
function (par .17.5.2) is set as HC-HP the heat pump and
the heating resistors tank charge is suspended; if the
comfort function is set as HC-HP 40°C, the tank charge
is limited, considering as DHW setpoint temperature the
minimum between the reduced setpoint temperature
and 40°C. Inut active (230V). The heat pump and the
resistors are enabled for the tank charge following the
standard logics.
- SG Ready 1: input signal nr 1 for the SG Ready standard
(see. Paragraph SMART GRID READY STANDARD)
- External Switch OFF signal: input signal to set the the
machine OFF. Every heat request, cooling request and
DHW service is stopped and antifreeze protection lo-
gics are active.
17.1.1
HV Input 2
- 0. Not defi ned: no function associated to the input. Fault
942 is displayed.
- 1. Absent: Input not enabled.
- 2. DLSG (load shedding): Input not active (0V). Heating
resistors are disabled in every cycles.
- 3. SG Ready 2: input signal nr 2 for the SG Ready stan-
dard (see. Paragraph SMART GRID READY STANDARD)
17.1.2
HV Input 3
- 0. Not active
- 1. PV integration active: Input not active (0V), no tank
integration from PV system. Input active (230V): if the
system is in stand-by, the DHW setpoint temperature is
incremented by the amount defi ned by the parameter
17.0.5 - PV Delta T DHW setpoint temp.
17.1.3
AUX Input 1
- 0. None
- 1. Humidistat: when the contact is closed, the heat pump
switches off
17.1.4
AUX Output 1 (AFR)
- 0. None
- 1. Fault alarm: the contact is closed in case of fault
- 2. Humidistat alarm: the output is closed when the AUX
1 is set as humidistat and it is closed.
- 3. External heat request: the contact is closed to gene-
rate an heat request to a external heat source instead of
the heating resistors.
- 4: Cooling Request: the contact is closed to generate a
cooling request to an external cooling source
17.1.5
AUX Output 2 (Come AUX1 OUT1)
69 / GB
Need help?
Do you have a question about the NIMBUS COMPACT M NET 40 M EXT and is the answer not in the manual?
Questions and answers