System operation strategy

Introduction
Electric preheater
Defrosting and fire-
place function
Bypass cooling and
summer mode
14
This section describes the operation strategy under a variety of conditions.
See more under user instructions on page 26
If a heating element is mounted it will ensure the heating of fresh outside air while also
reducing the need for defrosting.
The heating element can be enabled/disabled via the remote control (HRC3) in
installer mode
, if the preheating module is set to enable (active) via PC-Tool
during installation.
The heating element is added after the T1 sensor.
If the outside temperature is under -3°C or the supply air is under 16.5°C then
the heating element will function at 10%.
The heating element will increase or decrease the effect by 10% every minute
depending on the T1 or T2 temperature.
If 100% preheater power is not sufficient, boths will be lowered in a balanced
manner.
Setpoints cannot be changed.
During extremely cold periods with T1 temperatures under -3°C and the exhaust tem-
perature, T4, at less than +2°C there is a risk of condensate in the heat exchanger
freezing to ice, which is inadvisable.
The automatic function prevents this via the following procedure:
Heat is added if a heating element has been mounted.
The supply fan gradually reduces in speed until the minimum RPM is reached.
After 10 seconds at this speed the supply fan stops
while the extractor fan continues to circulate warmer air through the heat ex-
changer, thereby thawing any frost or ice that has formed.
Once T4 has again achieved over +8°C, the supply fan will start at minimum
RPM and gradually increase the speed until the original speed has been
achieved.
The procedure is repeated for as long as is necessary.
If the outside air, T1 is under or at -13°C for more than 4 minutes and 15 sec-
onds – also in defrost mode – the unit will stop for 30 minutes and then resume
normal operations.
This is not possible if the unit is equipped with a heating element.
The default defrost strategy can create underpressure in the house. This may cause
smoke from e.g. a fireplace to be drawn back into the house. Select fireplace mode in
PC-tool house settings. If selected unbalanced defrost is blocked ad the unit will stop
for 4 hours.
Setpoints cannot be changed.
During defrosting an HRC3 remote control will show: "dEF" in the display.
If the frost protection has stopped the unit, the T1 temperature on the display will flash.
See page 28