Page 1
FX6100, FX61002 Installation and Operation Manual Power Power Fault System FIRE Fault General TEST Fault Sounder General Disable Disable Fault 0786 G211013 DoP0228 EN54-2:1997 + A1:2006 EN54-4:1997 + A1:2002 + A2:2006...
Page 5
THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES . In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or other-wise for any special, indirect, incidental...
Page 6
That is why we offer you so many ways to get the support you need . Whether it is by phone, fax, or email, you can access Eaton’s support information 24 hours a day, seven days a week . Our wide range of services is listed below . You should contact your local distributor for product pricing, availability, ordering, expediting and repairs .
Page 7
RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE . DISPOSE OF THE USED BATTERIES ACCORDING TO THE INSTRUCTIONS . This product must only be disposed of in accordance with the WEEE directive . INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Fire panel/repeater panels to be installed and terminated . System to be powered up by installer and auto learn mode activated (see Auto Learn section) . System to be tested and verified by installer, prior to final commissioning . INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
5 . Final commissioning Minimum 2 weeks notice is required from receipt of Address Schedule and Commission request form . Eaton Lighting Service Engineer to attend site implement/ oversee the final commissioning procedures (see Commissioning section), in conjunction with the installer .
88H x 147W x 57D MSU840 Addressable Shop Unit Monitor 88H x 147W x 57D CSI350 Addressable Spur Isolator 88H x 147W x 57D CMIO353 Addressable Mains Relay 130H x 180W x 60D INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Equipment compatibility Sensors Loop wired sensors must be of the Eaton soft addressed analogue type . Eaton conventional detectors can be connected via a Zone Monitor Unit or Shop Unit interface . The connection of other detector types via a Zone Monitor Unit or Shop...
Page 12
. Relay circuits There are Relay circuits built-in the standard Panel . Additional relays can be added to the system by using Eaton soft addressing, Single Channel or 3 Channel Input/ Output Units . Relays/Auto-dialers and auxiliary equipment...
. For initial configuration or major system changes special PC configuration software is available enabling Eaton Lighting and Security personnel to do this more efficiently than can be achieved using the system screen .
Page 14
Similarly if a device is removed, the relevant address is saved as a spare address for future use, the addresses of the remaining devices are not altered . Multiple languages The Panel supports a large number of languages as standard . INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
: 1 .5 A Sounder Circuit Fuses (F1/2) : 1 .6 Amp (Quick Blow) End of line device : 210Ω + Diode AUX 1 Max Load : 1 Amp Fused (PTC2) : 1 .1A polyswitch INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Page 16
Flammability Rating : UL 94 V0 Total Number of knockouts : 11 Diameter of Knock out : 20mm TERMINAL BLOCKS : DO NOT USE EXCESSIVE FORCE WHEN TIGHTENING THE SCREWS ON THE TERMINAL BLOCK INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
The Panel has the facility to inhibit the operation of the output sounders, Output to Fire routing equipment and the output of the fire protecting equipment until one more confirmatory signals are received from different zones . This feature is programmable using Site Installer Software . INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Page 18
7. Loop feeds and returns should never be used within the same cable . Cable resistance Core diameter Typical FP200 resistance 1.0mm² 18.1 Ohms/km/Core 1.5mm² 12.1 Ohms/km/Core 2.5mm² 7.41 Ohms/km/Core 4.0mm² 4.61 Ohms/km/Core INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
. INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Page 20
Do not touch the electronics directly . Mounting the Backbox The Panel can be surface mounted and recessed . To surface mount; drill three holes and fix the backbox to the wall using suitable screw fixings . INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
. An additional warning label should be provided, depending on whether:- INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Page 22
1. The Zone Monitor Interface - Allows up to 20 conventional smoke detectors and unlimited Eaton call points. 2. The Spur Isolator Unit - Allows a zone of analogue Sensors and call points to be directly spurred off the loop . INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
. If the distance in the network exceeds 1KM the booster should be used . The booster requires 24V local supply, which can be connected to nearest Addressable Panel . INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
. Please ensure that all equipments connected to this output will only draw current when a fire condition exists . WARNING Do not exceed the rated output current . INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
. Special equipment is required for cleaning smoke detectors . Every 5 years Replace sealed lead acid battery . Cleaning: When cleaning the panel, use a moist cloth . Do not use solvents or harsh abrasives . INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
. This facility can be accessed via the engineering menu and can be switched on or off at any time as required . INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Page 27
Null Modem Cable Fault System A.serial Output FIRE Fault General TEST Fault Sounder General Disable Disable Fault B. USB Output USB Convertor Serial Rs232 port can be locatated on the main board INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
= S/C Normal O/C Fire = 12V No Fault 0V (short CCT) Fault = -O.6V-No Fire 24V Fire = 28V (Open Circuit, No Input) REPEAT FOR LOOP 2 = 22V (Device Fitted) 0V (Unused) INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Non-Latching-> device won’t latch in alarm condition, used in conjunction with isolates . Day / night Devices affected : Optical-Heat -> mode changes between heat or optoheat mode Heat -> mode changes between Heat A1R and Heat CS INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
This option is a manual intervention override, when enabled (check in box) the delay can be overridden from any call point on the loop when triggered . Daynight See coincidence detection below . INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
. When the ‘coincidence’ box is checked - the ‘Allocate device’ button allows the user to populate this list . INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Report fault to service dept System fault Monitors fire panel for faults Report fault to service dept Test Supervisor/engineer is testing the systems Report to system supervisor Sounder Indicates the sounder status Check with system supervisor INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
. When displaying the system menu on the Touch Screen, the last 5 lines of the display are shown in reverse text . INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Meeting Room 1, Building 1, 1st floor First Fire Loop: 1, Zone: 2, Type: Optical (150) System Healthy 10 Zones Active Print All Help Total Fires= 1 Tuesday dd-mm-yyyy Tuesday Dd-mmm-yyy 16:25.25 16:25.25 BST On BST On INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Page 35
Yes - autolearn loop 1 only Pre-addressed auto-learn Yes - autolearn loop 2 only Yes - autolearn loop 3 only Maintenance auto-learn Yes - autolearn loop 4 only Yes - autolearn all loops INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Page 36
PC download software. IMPORTANT: Load CDR from Laptop Do not click commission before pressing “Yes” on the This will erase the current CDR “Load CDR” screen. Do you want to continue? INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Page 37
Network Screen Cover System Details Commission devices to Load logo from PC hybrids (26V mode) Download CDR to Laptop Start PC program Press "OK" to continue or "Cancel" to exit Cancel INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Pre-alarm = Some smoke/heat but below fire threshold these warnings will appear and disappear Select “Yes” to evacuate the building . Supervisor FRE off This will activate ALL sounders and activate all panel relays Do you wish to continue? INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
AC = 0 View Alarms Disabled Zone: 0 Addresses: 0 Touch button to View list Select “yes” to silence Alarm . Supervisor FRE off This will silence ALL sounders Do you wish to continue? INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Alarms View Do you wish to continue? Disabled Faults 001 14:22:49 Mains Failure Faults = Short circuits, broken detectors etc. To remove faults from this list: 1) Fix Fault 2) Reset Panel INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
View list The individual buttons show which devices and the number of devices which have been disabled . Press one of the buttons to display detailed information for a particular category . INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Alarms Buzzer View Fires View Pre AC=100 View Alarms View Disabled Others Faults Enable/Disable Weekly Test Send Log to PC Print View Log Check Config. Lamp Test Send analogue values to PC INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Page 44
Touch “Disabled”button to Enable Enable all Devices? Zone 001 Zone 1 Enabled Do you want to continue? Zone 002 Zone 2 Disabled Zone 003 Zone 3 Disabled Zone 004 Zone 4 Enabled INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Page 45
Evacuate FRE off Alarms Buzzer Print All Log Records Print Fire Log Print Last 10 Log Records Print Fault Log Print Disablements Print Test Log Print Current Faults Exit Print Current Fires INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
View Log Lamp Test Check Config. Enter the Supervisor Mode and Select the “Others” Tab . Press “Lamp Test” . Supervisor FRE off Lamp Test LED’s will light in numerical order Cancel INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Awaiting Alarm Signal Weekly test Do you want to continue? Will reset after 4 minutes Cancel The panel will automatically return to the system healthy screen once the weekly test has been completed . INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
. Once the maximum 1000 events has been reached Panel will automatically overwrite the oldest event every time a new event is stored . The event log can only be reset by an approved service engineer . INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Replace Device Exit Supervisor Supervisor Silence Mute Press the Reset Evacuate FRE Off FRE Off Alarms Buzzer supervisor mode button at the top left of Print Exit the screen. Check Auto Config INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Change Device Auto Config. Supervisor FRE Off Check Auto Config Replace Device Exit Supervisor Supervisor FRE Off FRE Off Enter Loop 1 Address Select a Loop Loop 1 Loop 2 Exit Exit INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Touch "-" Button to remove a zone from test mode Zone 001 Building 1, Ground Test Zone 002 Building 1, 1st floor Zone 003 Building 1, 2nd floor Zone 004 Packing & Stores Zone 005 Building 2, basement INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Page 53
Global Flashing LED On/Off Sound Level Test Mode Do you want to continue? Sound Level Test Mode All sounders will now pulse 15 seconds on, 30 seconds off Touch “Stop” button to stop test Stop INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Test Device Test Zone Select “Global Flashing LED On/ Sound Level Test Mode Off” from the Test Menu Screen . One Man Walk Test Global Flashing LED On/Off Global flashing LED’s Flashing INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Sound Level Test Mode One Man Walk Test Global Flashing LED On/Off * Feature is outside EN54 spec One Man Walk Test One Man Walk Test Do you want to continue? Awaiting Alarm Signal Stop INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Number of Panels Erase Log in Network Screen Cover System Details Commission devices to Load logo from PC hybrids (26V mode) This will delete all log entries Do you want to continue INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Configure Menu Screen . Auto Learn Change Panel Number Number of Panels Erase Log and Reset in Network System Detail Screen Cover Load logo from PC Italian Mode Load logo from PC Exit INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Loop: 1, Zone: 1, Type: Opto/thermal Cancel 005 Device 5, Zone 1 Loop: 1, Zone: 1, Type: Opto/thermal Note: go to command can be used to jump to a speci c address INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Number of Panels Erase Log in Network ok 0 Screen Cover System Details Commission devices to Cancel Load logo from PC hybrids (26V mode) Number of Panels in Network ......4 5 6 INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Change Panel Number Number of Panels Erase Log in Network System Details Screen Cover Commission devices to Load logo from PC hybrids (26V mode) Service Reset Exit FRE off Installed Not Required INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Network Configure Zones Language Change Passcode Day/Night Italian Mode Network Protocol Service Mute Reset Exit FRE off Buzzer Italian Mode T1:Call Point Delay 0 mins,0 secs T2:Detector Delay 0 mins Enabled Disabled INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Language Then press T1/T2 Change Passcode Day/Night Italian Mode Network Protocol Service Exit Reset FRE off Sound Settings T1/T2 Auxillary Board Alarm Verification Feature FRE impedance band FRE double-knock Override Sounder tone INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Press panel outputs - NOTE Interface Inputs/ Auxillary Board Alarm Verification Feature Interface Outputs are FRE impedance band Panel Outputs only used in certain export markets . FRE double-knock Override Sounder tone INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Network Configure Zones Language Change Passcode Day/Night Italian Mode Network Protocol Service Exit Reset FRE off Sound Settings T1/T2 Auxillary Board Alarm Verification Feature FRE impedance band FRE double-knock Override Sounder tone INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Configure Heat Detectors Auxillary Board Alarm Verification Feature Change Text Network FRE double-knock override Configure Zone Language Sounder tone Day/Night Change Pascode Service Exit Reset FRE off AVF On/Off AVF length AVF Zones INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
This will effect all sounders Volume Medium High Sound Service Service Exit Reset Exit Reset FRE off FRE off Sound This will effect all sounders Volume Slow Woop Two Tone Sound Continuous INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Set the Time Using the Buttons Shown Below . Service Cancel Reset FRE Off Current Time: Hour Mins Mins 10:16:12 Hour Mins Mins BST On Current Date: Month Year Wednesday Month Year dd-mmm-yyyy INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
FRE Off Enter the name for Zone 2 Exit Zone 2 ..................Zone 001 Zone 1 Zone 002 Zone 2 Zone 003 Zone 3 Zone 004 Zone 4 CAPS OTHER SPACE CANCEL INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Loop: 1, Zone: 1, Type : Opto/thermal 004 Device 4, Zone 1 Loop: 1, Zone: 1, Type : Opto/thermal CAPS 005 Device 5, Zone 1 SPACE CANCEL OTHER Loop: 1, Zone: 1, Type : Opto/thermal INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Italian Mode Network Protocol Press “Change Panel Text” . Service Exit Reset FRE Off Change address text Change zone text Change Panel Text Correct Panel Text DF6000 ..................CAPS OTHER SPACE CANCEL INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Change Engineering code ......7 8 9 Verify New Code: Change User code ......ok 0 Cancel Passcode is not correct. Verification is incorrect New Password accepted No change made No change made Saved INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Configure Heat Detectors Change Text Network Configure Zones Language Change Passcode Day/Night Italian Mode Network Protocol Service Exit Reset FRE Off Add Zone Delete Zone Add Device Delete Device Add Zone ? INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Service Reset FRE Off Exit Touch row to delete Zone 001 Zone 1 Zone 002 Zone 2 Zone 003 Zone 3 Zone 004 Zone 4 Confirm or Cancel Deletion Delete Zone 2? INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Change Text Network Configure Zones Language Change Passcode Day/Night Italian Mode Network Protocol Service Exit Receive message over network FRE Off Reset Network Evacuate Network Network Silence Network Fire Network Fault Network Pre-Alarm INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Network Protocol Select required Language English Français Deutsch Nederlands Italiano Português Nederlands (BE) Cesky Dansk Slovensky Magyar Slovenski Hrvatski Lietuva Svenska Russian Greek Viê · t Eesti Afrikaans Suomi Türkçe Arabic Polski Latviešu INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Change Passcode Day/Night Italian Mode Network Protocol Service Exit Reset FRE off Delay (minutes) Service Reset Exit FRE off Delay (minutes) Exit Feature is outside EN54 spec Exit Feature is outside EN54 spec INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
. Press supervisor mode and the password entry screen will be displayed, type in the passcode and press Ok . If the wrong password is entered three times further access to the system is denied . INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
E E a a r r t t h h s s c c r r e e e e n n o o f f c c a a b b l l e e t t o o b b e e c c o o n n t t i i n n u u o o u u s s b b e e t t w w e e e e n n s s e e n n s s o o r r s s INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Two tone 610 / 910Hz @ 1Hz cycle Slow whoop 500-1200Hz in 3.5 seconds / 0.5secs gap S S + + F F + + Due to restricted access space, do not use excessive cable in this area. INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
. Earth screen must be continuous along entire length of loop . Analogue Addressable Loop ote: Care should be taken to ensure the cable does not put stress on the circuit board INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
A A n n a a l l o o g g u u e e A A d d d d r r e e s s s s a a b b l l e e L L o o o o p p INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Base terminal 1, 2, 3 and 4 not used . All wiring terminates as shown above . ote: WARNING Do NOT use high voltage testers if ANY equipment is connected to the system . Earth screen must be continuous along entire length of loop . INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
2 . Soft addressed . Standard connections WARNING Do NOT use high voltage testers if ANY equipment is connected to the system . Earth screen must be continuous along entire length of loop . INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
2 . Soft addressed . Standard connections WARNING Do NOT use high voltage testers if ANY equipment is connected to the system . Earth screen must be continuous along entire length of loop . INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
2 . The end of line resistor must always be fitted, even if the inputs are unused 3 . Monitored inputs can detect open or short circuit faults 4 . Output relays are volt-free contacts and are not monitored INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
I I N N P P U U T T ote: 1 . Only connect cable screen to its adjacent earth terminal 2 . The end of line resistor must always be fitted, even if the spur is unused INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
4 . Maximum spur length - See BS5839 Pt1:2002 for Zone Coverage 5 . Maximum number of call points allowed is unlimited 6 . Detector zone end of line device is EOLM-1 (supplied) 7 . Callpoint zone has end of line resistor INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
3 . Only connect cable screen to its adjacent earth terminal 4 . The end of line resistor must always be fitted, even if the spur is unused 5 . Maximum spur length – See BS5839 Pt1:2001 for Zone Coverage INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
4 . Maximum spur length - See BS5839 Pt1:2002 for Zone Coverage 5 . Maximum number of call points allowed is unlimited 6 . Detector zone end of line device is EOLM-1 7 . Callpoint zone has end of line resistor INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
1 . Only connect cable screen to its adjacent earth terminal 2 . For maximum spur length / load see BS5839 Pt1:2002 3 . This unit can only be used with Eaton CAB300 and CDB300/I Sensor bases and compatible sensors...
B B A A T T T T E E R R Y Y ote: 1 . Only connect cable screen to its adjacent earth terminal 2 . The end of line resistors must always be fitted, even if the sounder circuits are unused INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Recommended Loop Cable Type: FIRETUF , FP200, MICC No addressing of the interface is required . See control panel operation for details . There are no serviceable parts so no maintenance procedures apply INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
JIU872 Standard connections ote: 1 . This unit can only be used with Eaton FXN520 detector base and compatible detectors 2 . Only connect cable screen to its adjacent earth terminal 3 . The end of line resistor must always be fitted, even if the spur is unused 4 .
1 . Only connect cable screen to its adjacent earth terminal 2 . The end of line resistor provided must always be fitted, even if the input is unused 3 . Monitored inputs can detect open or short circuit faults INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Page 101
Loop In- EARTH Earth Loop Out+ Loop Out- MJOM Earth ote: 1 . Only connect cable screen to its adjacent earth terminal 2 . Output relay are volt-free contacts and are not monitored INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Page 102
Section 4: Appendix INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
Page 103
Section 4: Appendix INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...