FX6100, FX61002
Installation and Operation Manual
Power
General
General
Disable
Power
ON
Fault
System
FIRE
Fault
TEST
Fault
Sounder
Disable
Fault
16
VdS
0786
G211013
DoP0228
EN54-2:1997 + A1:2006
EN54-4:1997 + A1:2002 + A2:2006

Advertisement

Table of Contents
loading

Summary of Contents for Eaton FX6100

  • Page 1 FX6100, FX61002 Installation and Operation Manual Power Power Fault System FIRE Fault General TEST Fault Sounder General Disable Disable Fault 0786 G211013 DoP0228 EN54-2:1997 + A1:2006 EN54-4:1997 + A1:2002 + A2:2006...
  • Page 2: Table Of Contents

    Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40 INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 3 Configure zones . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .76 INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 4 Technical I/O Unit Wiring (CFC301) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .107 INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 5 THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES . In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or other-wise for any special, indirect, incidental...
  • Page 6 That is why we offer you so many ways to get the support you need . Whether it is by phone, fax, or email, you can access Eaton’s support information 24 hours a day, seven days a week . Our wide range of services is listed below . You should contact your local distributor for product pricing, availability, ordering, expediting and repairs .
  • Page 7 RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE . DISPOSE OF THE USED BATTERIES ACCORDING TO THE INSTRUCTIONS . This product must only be disposed of in accordance with the WEEE directive . INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 8: Section 1: System Installation And Design

    Fire panel/repeater panels to be installed and terminated . System to be powered up by installer and auto learn mode activated (see Auto Learn section) . System to be tested and verified by installer, prior to final commissioning . INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 9: System Design Guidelines

    5 . Final commissioning Minimum 2 weeks notice is required from receipt of Address Schedule and Commission request form . Eaton Lighting Service Engineer to attend site implement/ oversee the final commissioning procedures (see Commissioning section), in conjunction with the installer .
  • Page 10: Compatible Equipment

    88H x 147W x 57D MSU840 Addressable Shop Unit Monitor 88H x 147W x 57D CSI350 Addressable Spur Isolator 88H x 147W x 57D CMIO353 Addressable Mains Relay 130H x 180W x 60D INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 11: Equipment Compatibility

    Equipment compatibility Sensors Loop wired sensors must be of the Eaton soft addressed analogue type . Eaton conventional detectors can be connected via a Zone Monitor Unit or Shop Unit interface . The connection of other detector types via a Zone Monitor Unit or Shop...
  • Page 12 . Relay circuits There are Relay circuits built-in the standard Panel . Additional relays can be added to the system by using Eaton soft addressing, Single Channel or 3 Channel Input/ Output Units . Relays/Auto-dialers and auxiliary equipment...
  • Page 13: System Overview

    . For initial configuration or major system changes special PC configuration software is available enabling Eaton Lighting and Security personnel to do this more efficiently than can be achieved using the system screen .
  • Page 14 Similarly if a device is removed, the relevant address is saved as a spare address for future use, the addresses of the remaining devices are not altered . Multiple languages The Panel supports a large number of languages as standard . INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 15: Technical Specification

    : 1 .5 A Sounder Circuit Fuses (F1/2) : 1 .6 Amp (Quick Blow) End of line device : 210Ω + Diode AUX 1 Max Load : 1 Amp Fused (PTC2) : 1 .1A polyswitch INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 16 Flammability Rating : UL 94 V0 Total Number of knockouts : 11 Diameter of Knock out : 20mm TERMINAL BLOCKS : DO NOT USE EXCESSIVE FORCE WHEN TIGHTENING THE SCREWS ON THE TERMINAL BLOCK INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 17: Optional Functions As Per En54 P2&4

    The Panel has the facility to inhibit the operation of the output sounders, Output to Fire routing equipment and the output of the fire protecting equipment until one more confirmatory signals are received from different zones . This feature is programmable using Site Installer Software . INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 18 7. Loop feeds and returns should never be used within the same cable . Cable resistance Core diameter Typical FP200 resistance 1.0mm² 18.1 Ohms/km/Core 1.5mm² 12.1 Ohms/km/Core 2.5mm² 7.41 Ohms/km/Core 4.0mm² 4.61 Ohms/km/Core INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 19: Installation

    . INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 20 Do not touch the electronics directly . Mounting the Backbox The Panel can be surface mounted and recessed . To surface mount; drill three holes and fix the backbox to the wall using suitable screw fixings . INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 21: External Connections

    . An additional warning label should be provided, depending on whether:- INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 22 1. The Zone Monitor Interface - Allows up to 20 conventional smoke detectors and unlimited Eaton call points. 2. The Spur Isolator Unit - Allows a zone of analogue Sensors and call points to be directly spurred off the loop . INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 23: Networking

    . If the distance in the network exceeds 1KM the booster should be used . The booster requires 24V local supply, which can be connected to nearest Addressable Panel . INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 24: Input/Outputs

    . Please ensure that all equipments connected to this output will only draw current when a fire condition exists . WARNING Do not exceed the rated output current . INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 25: Maintainance

    . Special equipment is required for cleaning smoke detectors . Every 5 years Replace sealed lead acid battery . Cleaning: When cleaning the panel, use a moist cloth . Do not use solvents or harsh abrasives . INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 26: Section 2: Commissioning

    . This facility can be accessed via the engineering menu and can be switched on or off at any time as required . INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 27 Null Modem Cable Fault System A.serial Output FIRE Fault General TEST Fault Sounder General Disable Disable Fault B. USB Output USB Convertor Serial Rs232 port can be locatated on the main board INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 28: Panel Fault Finding

    = S/C Normal O/C Fire = 12V No Fault 0V (short CCT) Fault = -O.6V-No Fire 24V Fire = 28V (Open Circuit, No Input) REPEAT FOR LOOP 2 = 22V (Device Fitted) 0V (Unused) INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 29: Pc Comissioning Software

    Non-Latching-> device won’t latch in alarm condition, used in conjunction with isolates . Day / night Devices affected : Optical-Heat -> mode changes between heat or optoheat mode Heat -> mode changes between Heat A1R and Heat CS INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 30: Device Outputs

    This option is a manual intervention override, when enabled (check in box) the delay can be overridden from any call point on the loop when triggered . Daynight See coincidence detection below . INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 31: Panel Outputs

    . When the ‘coincidence’ box is checked - the ‘Allocate device’ button allows the user to populate this list . INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 32: Section 3: Panel Controls & Indicators

    Report fault to service dept System fault Monitors fire panel for faults Report fault to service dept Test Supervisor/engineer is testing the systems Report to system supervisor Sounder Indicates the sounder status Check with system supervisor INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 33: Touch Screen Display

    . When displaying the system menu on the Touch Screen, the last 5 lines of the display are shown in reverse text . INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 34: Panel Operation

    Meeting Room 1, Building 1, 1st floor First Fire Loop: 1, Zone: 2, Type: Optical (150) System Healthy 10 Zones Active Print All Help Total Fires= 1 Tuesday dd-mm-yyyy Tuesday Dd-mmm-yyy 16:25.25 16:25.25 BST On BST On INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 35 Yes - autolearn loop 1 only Pre-addressed auto-learn Yes - autolearn loop 2 only Yes - autolearn loop 3 only Maintenance auto-learn Yes - autolearn loop 4 only Yes - autolearn all loops INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 36 PC download software. IMPORTANT: Load CDR from Laptop Do not click commission before pressing “Yes” on the This will erase the current CDR “Load CDR” screen. Do you want to continue? INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 37 Network Screen Cover System Details Commission devices to Load logo from PC hybrids (26V mode) Download CDR to Laptop Start PC program Press "OK" to continue or "Cancel" to exit Cancel INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 38: Public Access Level 1

    Lp: 1, Ad: 4, Z: 1, Opto/thermal [69] 005 12:35:59 Fault! : Device5 005 03-Jun-03 12:51 Warning! : Device5 Lp: 1, Ad: 4, Z: 1, Opto/thermal [69] Lp: 1, Ad: 5, Z: 1, Opto/thermal [69] INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 39: Evacuate (Access Level 2)

    Pre-alarm = Some smoke/heat but below fire threshold these warnings will appear and disappear Select “Yes” to evacuate the building . Supervisor FRE off This will activate ALL sounders and activate all panel relays Do you wish to continue? INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 40: Silence Alarms

    AC = 0 View Alarms Disabled Zone: 0 Addresses: 0 Touch button to View list Select “yes” to silence Alarm . Supervisor FRE off This will silence ALL sounders Do you wish to continue? INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 41: Mute Buzzer

    Alarms View Do you wish to continue? Disabled Faults 001 14:22:49 Mains Failure Faults = Short circuits, broken detectors etc. To remove faults from this list: 1) Fix Fault 2) Reset Panel INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 42: Pre-Alarms

    View list The individual buttons show which devices and the number of devices which have been disabled . Press one of the buttons to display detailed information for a particular category . INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 43: Faults

    Alarms Buzzer View Fires View Pre AC=100 View Alarms View Disabled Others Faults Enable/Disable Weekly Test Send Log to PC Print View Log Check Config. Lamp Test Send analogue values to PC INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 44 Touch “Disabled”button to Enable Enable all Devices? Zone 001 Zone 1 Enabled Do you want to continue? Zone 002 Zone 2 Disabled Zone 003 Zone 3 Disabled Zone 004 Zone 4 Enabled INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 45 Evacuate FRE off Alarms Buzzer Print All Log Records Print Fire Log Print Last 10 Log Records Print Fault Log Print Disablements Print Test Log Print Current Faults Exit Print Current Fires INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 46: Lamp Test

    View Log Lamp Test Check Config. Enter the Supervisor Mode and Select the “Others” Tab . Press “Lamp Test” . Supervisor FRE off Lamp Test LED’s will light in numerical order Cancel INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 47: Weekly Test

    Awaiting Alarm Signal Weekly test Do you want to continue? Will reset after 4 minutes Cancel The panel will automatically return to the system healthy screen once the weekly test has been completed . INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 48: Viewing Events

    . Once the maximum 1000 events has been reached Panel will automatically overwrite the oldest event every time a new event is stored . The event log can only be reset by an approved service engineer . INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 49: Check Auto Config

    Replace Device Exit Supervisor Supervisor Silence Mute Press the Reset Evacuate FRE Off FRE Off Alarms Buzzer supervisor mode button at the top left of Print Exit the screen. Check Auto Config INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 50: Replace Device

    Change Device Auto Config. Supervisor FRE Off Check Auto Config Replace Device Exit Supervisor Supervisor FRE Off FRE Off Enter Loop 1 Address Select a Loop Loop 1 Loop 2 Exit Exit INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 51: Test Device (Access Level 3)

    Loop: 1, Zone: 2, Type: Optical 003 Storage/archive, Building 1, 1st floor Loop: 1, Zone: 2, Type: Optical 004 Meeting Room 1, Building 1, 1st floor Loop: 1, Zone: 2, Type: Optical INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 52: Test Zone

    Touch "-" Button to remove a zone from test mode Zone 001 Building 1, Ground Test Zone 002 Building 1, 1st floor Zone 003 Building 1, 2nd floor Zone 004 Packing & Stores Zone 005 Building 2, basement INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 53 Global Flashing LED On/Off Sound Level Test Mode Do you want to continue? Sound Level Test Mode All sounders will now pulse 15 seconds on, 30 seconds off Touch “Stop” button to stop test Stop INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 54: Global Flashing Led On/Off

    Test Device Test Zone Select “Global Flashing LED On/ Sound Level Test Mode Off” from the Test Menu Screen . One Man Walk Test Global Flashing LED On/Off Global flashing LED’s Flashing INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 55: One Man Walk Test

    Sound Level Test Mode One Man Walk Test Global Flashing LED On/Off * Feature is outside EN54 spec One Man Walk Test One Man Walk Test Do you want to continue? Awaiting Alarm Signal Stop INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 56: Commission: Load Cdr From Laptop

    Number of Panels Erase Log in Network Screen Cover System Details Commission devices to Load logo from PC hybrids (26V mode) This will delete all log entries Do you want to continue INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 57: System Details

    Print Exit Reset FRE off Loop 1 Loop 2 Loop 3 Loop 4 Voice Annunciator Repeater ZMU/{SUM Beam Detector Technical Timer Access Control Emerg.Light.Module Carbon Monoxide Page 1 Page 2 Page 3 INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 58: Load Logo From Pc

    Configure Menu Screen . Auto Learn Change Panel Number Number of Panels Erase Log and Reset in Network System Detail Screen Cover Load logo from PC Italian Mode Load logo from PC Exit INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 59: Analogue Level

    Loop: 1, Zone: 1, Type: Opto/thermal Cancel 005 Device 5, Zone 1 Loop: 1, Zone: 1, Type: Opto/thermal Note: go to command can be used to jump to a speci c address INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 60: Change Panel Number

    Number of Panels Erase Log in Network ok 0 Screen Cover System Details Commission devices to Cancel Load logo from PC hybrids (26V mode) Number of Panels in Network ......4 5 6 INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 61: Screen Cover

    Change Panel Number Number of Panels Erase Log in Network System Details Screen Cover Commission devices to Load logo from PC hybrids (26V mode) Service Reset Exit FRE off Installed Not Required INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 62: Italian Mode

    Network Configure Zones Language Change Passcode Day/Night Italian Mode Network Protocol Service Mute Reset Exit FRE off Buzzer Italian Mode T1:Call Point Delay 0 mins,0 secs T2:Detector Delay 0 mins Enabled Disabled INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 63: Programming I/O And Sounders T1

    Language Then press T1/T2 Change Passcode Day/Night Italian Mode Network Protocol Service Exit Reset FRE off Sound Settings T1/T2 Auxillary Board Alarm Verification Feature FRE impedance band FRE double-knock Override Sounder tone INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 64: Programming I/O And Sounders. Panel Outputs

    Press panel outputs - NOTE Interface Inputs/ Auxillary Board Alarm Verification Feature Interface Outputs are FRE impedance band Panel Outputs only used in certain export markets . FRE double-knock Override Sounder tone INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 65: Programming I/O And Sounders. Auxiliary Board

    Network Configure Zones Language Change Passcode Day/Night Italian Mode Network Protocol Service Exit Reset FRE off Sound Settings T1/T2 Auxillary Board Alarm Verification Feature FRE impedance band FRE double-knock Override Sounder tone INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 66: Programming I/O And Sounders Alarm Verification

    Configure Heat Detectors Auxillary Board Alarm Verification Feature Change Text Network FRE double-knock override Configure Zone Language Sounder tone Day/Night Change Pascode Service Exit Reset FRE off AVF On/Off AVF length AVF Zones INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 67: Sound Settings

    This will effect all sounders Volume Medium High Sound Service Service Exit Reset Exit Reset FRE off FRE off Sound This will effect all sounders Volume Slow Woop Two Tone Sound Continuous INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 68: Change Date/Time

    Set the Time Using the Buttons Shown Below . Service Cancel Reset FRE Off Current Time: Hour Mins Mins 10:16:12 Hour Mins Mins BST On Current Date: Month Year Wednesday Month Year dd-mmm-yyyy INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 69: Change Zone Text

    FRE Off Enter the name for Zone 2 Exit Zone 2 ..................Zone 001 Zone 1 Zone 002 Zone 2 Zone 003 Zone 3 Zone 004 Zone 4 CAPS OTHER SPACE CANCEL INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 70: Change Text

    Loop: 1, Zone: 1, Type : Opto/thermal 004 Device 4, Zone 1 Loop: 1, Zone: 1, Type : Opto/thermal CAPS 005 Device 5, Zone 1 SPACE CANCEL OTHER Loop: 1, Zone: 1, Type : Opto/thermal INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 71: Change Panel Text

    Italian Mode Network Protocol Press “Change Panel Text” . Service Exit Reset FRE Off Change address text Change zone text Change Panel Text Correct Panel Text DF6000 ..................CAPS OTHER SPACE CANCEL INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 72: Configure Zones

    Loop: 1, Zone: 1, Type : Opto/thermal the selected zone. 004 Device 4, Zone 2 Loop: 1, Zone: 2, Type : Opto/thermal 005 Device 5, Zone2 Loop: 1, Zone: 2, Type : Opto/thermal INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 73: Change Passcode

    Change Engineering code ......7 8 9 Verify New Code: Change User code ......ok 0 Cancel Passcode is not correct. Verification is incorrect New Password accepted No change made No change made Saved INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 74: Add Zone

    Configure Heat Detectors Change Text Network Configure Zones Language Change Passcode Day/Night Italian Mode Network Protocol Service Exit Reset FRE Off Add Zone Delete Zone Add Device Delete Device Add Zone ? INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 75: Delete Zone

    Service Reset FRE Off Exit Touch row to delete Zone 001 Zone 1 Zone 002 Zone 2 Zone 003 Zone 3 Zone 004 Zone 4 Confirm or Cancel Deletion Delete Zone 2? INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 76: Add Device

    FRE Off Loop 1 Loop 2 Loop 3 Loop 4 Exit Confirm New Device and Loop Loop 2 Loop 2 Saving... Scanning Loop Loop 1, Address 30, Type [device type] Exit Exit INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 77: Delete Device

    005 Device 5, Zone 1 Loop: 1, Zone: 1, Type : Opto/thermal Confirm or Cancel Deletion Delete Device 3? Device 3 Loop 1, Address 3, Device Type Opto/thermal Yes, but keep settings INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 78: Configure Heat Detectors

    Loop: 1, Zone: 2, Type : Opto/thermal 005 Device 5, Zone 1 Loop: 1, Zone: 1, Type : Opto/thermal Select appropriate detector class . Service Reset FRE Off Thermal A1R Thermal BS Thermal CS Exit INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 79: Network Filter

    Change Text Network Configure Zones Language Change Passcode Day/Night Italian Mode Network Protocol Service Exit Receive message over network FRE Off Reset Network Evacuate Network Network Silence Network Fire Network Fault Network Pre-Alarm INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 80: Language

    Network Protocol Select required Language English Français Deutsch Nederlands Italiano Português Nederlands (BE) Cesky Dansk Slovensky Magyar Slovenski Hrvatski Lietuva Svenska Russian Greek Viê · t Eesti Afrikaans Suomi Türkçe Arabic Polski Latviešu INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 81: Day/Night

    Change Passcode Day/Night Italian Mode Network Protocol Service Exit Reset FRE off Delay (minutes) Service Reset Exit FRE off Delay (minutes) Exit Feature is outside EN54 spec Exit Feature is outside EN54 spec INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 82: Password Protection

    . Press supervisor mode and the password entry screen will be displayed, type in the passcode and press Ok . If the wrong password is entered three times further access to the system is denied . INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 83: Section 4: Appendix

    Section 4: Appendix Section 4: Appendix System wiring INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 84: Detector Base Wiring (Cab300)

    E E a a r r t t h h s s c c r r e e e e n n o o f f c c a a b b l l e e t t o o b b e e c c o o n n t t i i n n u u o o u u s s b b e e t t w w e e e e n n s s e e n n s s o o r r s s INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 85: Call Point Wiring (Cbg370S/Cbg370Wp)

    Two tone 610 / 910Hz @ 1Hz cycle Slow whoop 500-1200Hz in 3.5 seconds / 0.5secs gap S S + + F F + + Due to restricted access space, do not use excessive cable in this area. INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 86: Loop Powered Beacon Wiring (Cab382)

    . Earth screen must be continuous along entire length of loop . Analogue Addressable Loop ote: Care should be taken to ensure the cable does not put stress on the circuit board INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 87: Ip66 Wall Sounder Wiring (Cas381Wp , Casb383-Wp)

    A A n n a a l l o o g g u u e e A A d d d d r r e e s s s s a a b b l l e e L L o o o o p p INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 88: Base Sounder Vad (Casbb394)

    Base terminal 1, 2, 3 and 4 not used . All wiring terminates as shown above . ote: WARNING Do NOT use high voltage testers if ANY equipment is connected to the system . Earth screen must be continuous along entire length of loop . INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 89: Wall Sounder Vad (Casb393)

    2 . Soft addressed . Standard connections WARNING Do NOT use high voltage testers if ANY equipment is connected to the system . Earth screen must be continuous along entire length of loop . INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 90: Ip66 Wall Sounder Vad (Casb393Wp)

    2 . Soft addressed . Standard connections WARNING Do NOT use high voltage testers if ANY equipment is connected to the system . Earth screen must be continuous along entire length of loop . INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 91: Way Input Output Unit (Cio351, Cio351S, Cio351Sst)

    2 . The end of line resistor must always be fitted, even if the inputs are unused 3 . Monitored inputs can detect open or short circuit faults 4 . Output relays are volt-free contacts and are not monitored INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 92: Channel Mains Rated I/O Unit Wiring (Cmio353)

    I I N N P P U U T T ote: 1 . Only connect cable screen to its adjacent earth terminal 2 . The end of line resistor must always be fitted, even if the spur is unused INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 93: Zone Monitor Unit Wiring (Czmu352)

    4 . Maximum spur length - See BS5839 Pt1:2002 for Zone Coverage 5 . Maximum number of call points allowed is unlimited 6 . Detector zone end of line device is EOLM-1 (supplied) 7 . Callpoint zone has end of line resistor INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 94: Intrinsically Safe Zone Monitor Unit Wiring (Czmu352-Is)

    3 . Only connect cable screen to its adjacent earth terminal 4 . The end of line resistor must always be fitted, even if the spur is unused 5 . Maximum spur length – See BS5839 Pt1:2001 for Zone Coverage INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 95: Shop Monitor Unit Wiring (Msu840)

    4 . Maximum spur length - See BS5839 Pt1:2002 for Zone Coverage 5 . Maximum number of call points allowed is unlimited 6 . Detector zone end of line device is EOLM-1 7 . Callpoint zone has end of line resistor INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 96: Spur Isolator Wiring (Csi350)

    1 . Only connect cable screen to its adjacent earth terminal 2 . For maximum spur length / load see BS5839 Pt1:2002 3 . This unit can only be used with Eaton CAB300 and CDB300/I Sensor bases and compatible sensors...
  • Page 97: Way Sounder Controller Wiring (Csc354Cpr)

    B B A A T T T T E E R R Y Y ote: 1 . Only connect cable screen to its adjacent earth terminal 2 . The end of line resistors must always be fitted, even if the sounder circuits are unused INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 98: 4-20Ma Interface Wiring (Cgi420, Cit420, Cgi420R, Cit420R)

    Recommended Loop Cable Type: FIRETUF , FP200, MICC No addressing of the interface is required . See control panel operation for details . There are no serviceable parts so no maintenance procedures apply INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 99: Micro Zone Monitor Module Wiring (Miu872)

    JIU872 Standard connections ote: 1 . This unit can only be used with Eaton FXN520 detector base and compatible detectors 2 . Only connect cable screen to its adjacent earth terminal 3 . The end of line resistor must always be fitted, even if the spur is unused 4 .
  • Page 100: Micro Input Module Wiring (Mcim)

    1 . Only connect cable screen to its adjacent earth terminal 2 . The end of line resistor provided must always be fitted, even if the input is unused 3 . Monitored inputs can detect open or short circuit faults INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 101 Loop In- EARTH Earth Loop Out+ Loop Out- MJOM Earth ote: 1 . Only connect cable screen to its adjacent earth terminal 2 . Output relay are volt-free contacts and are not monitored INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 102 Section 4: Appendix INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 103 Section 4: Appendix INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com...
  • Page 104 Eaton Electrical Systems Ltd . Wheatley Hall Road Doncaster South Yorkshire DN2 4NB Eaton EMEA Headquarters Route de la Longeraie 7 1110 Morges, Switzerland Eaton .eu © 2018 Eaton Eaton is a registered trademark. All Rights Reserved Publication No . 25-16329-B...