C. Full Reline With Outside Air - Horizontal
CAUTION
Never draw outside combustion air from:
Wall, floor or ceiling cavity
Enclosed space such as an attic or garage
Figure 19.1
NOTE: In Canada, where passage through a wall or
partition of combustible construction is desired,
the installation shall conform to CAN/CSA-B365.
19
NOTE; Use non-combustible
materials around exhaust vent
pipe and seal all edges with
non-flammable insulation such
as mineral wool or ceramic.
Do not use high temperature
caulking materials to seal any
edge to prevent furture
serviceability.
Fire Risk.
Inspection of Chimney:
Masonry chimney must be in
good condition.
Meets minimum standard of NFPA 211
Factory-built chimney must be a minimum
6 inch (152mm) UL103 HT.
Outside Air through Rear
Wall (Horizontal)
NOTE:
Illustrations reflect typical installations and are FOR
DESIGN PURPOSES ONLY.
Illustrations/diagrams are not drawn to scale.
Actual installation may vary due to individual
design preference.
7027-804G