DX80...C Wiring
Wiring power to the DX80...C models varies depending the power requirements of the model. Connecting dc power to the communication
pins (Tx/Rx) will cause permanent damage. For FlexPower devices, do not apply more than 5.5V to the gray wire.
Terminal Label Gateway, DX85
V+
10 to 30V dc
Tx/+
RS485 / D1 / B / +
V-
dc common (GND)
Rx/-
RS485 / D0 / A / -
B+

Terminal Blocks

IP67 Housing
GND
GND
DO6
DI6
DO5
DI5
DO4
DI4
DI3
DO3
DO2
DI2
DO1
DI1
Wiring Diagrams for Discrete Inputs
Connecting dc power to the communication pins will cause permanent damage. For the DX8x...C models, PWR in the wiring diagram
refers to V+ on the wiring board and GND in the wiring diagram refers to V- on the wiring board.
Discrete Input Wiring for PNP Sensors
PWR
10-30V dc
DIx
Wiring Diagrams for Discrete Outputs
Connecting dc power to the communication pins will cause permanent damage. For the DX8x...C models, PWR in the wiring diagram
refers to V+ on the wiring board and GND in the wiring diagram refers to V- on the wiring board.
Discrete Output Wiring (PNP)
PWR
DOx
Load
GND
4
10 to 30V dc Powered Nodes
10 to 30V dc
dc common (GND)
IP20 Housing
DI1
DI2
DI3
DI4
DI5
DI6
V+
V-
V-
10-30V dc
dc common
www.bannerengineering.com - tel: 763-544-3164
Battery Powered Nodes
dc common (GND)
3.6 to 5.5V dc
DIx. Discrete IN x.
DOx. Discrete OUT x.
DO1
DO2
GND. Ground/dc common connection.
DO3
PWR. Power, 10 to 30V dc power connection.
DO4
DO5
RX/-. Serial comms line
DO6
Tx/+
TX/+. Serial comms line
Rx/-
V+. Power, 10 to 30V dc power connection.
V+
V-. Ground/dc common connection.
Discrete Input Wiring for NPN Sensors
DIx
GND
dc common
SureCross DX80 Node