Banner SureCross DX80 Series Manual page 7

Node
Hide thumbs Also See for SureCross DX80 Series:
Table of Contents

Advertisement

SureCross DX80 Node
Link Timeout
Gateway: Configurable
Node: Defined by Gateway
Radio range is with the 2 dB antenna that ships with the product.
High-gain antennas are available, but the range depends on the
environment and line of sight. To determine the range of your wire-
less network, perform a Site Survey.
Discrete Inputs
Rating: 3 mA max current at 30V dc
Sample Rate: 62.5 milliseconds
Report Rate: On change of state
Discrete Input ON Condition
PNP: Greater than 8V
NPN: Less than 0.7V
Discrete Input OFF Condition
PNP: Less than 5V
NPN: Greater than 2V or open
Analog Inputs
Rating: 10V
Impedance: 100 Ohms
Sample Rate: 62.5 milliseconds
Report Rate: 1 second or On Change of State (1%
change in value)
Accuracy: 0.1% of full scale +0.01% per °C
Resolution: 12-bit
Ratings
DX80 models:IEC IP67; NEMA 6; (See UL section be-
low for any applicable UL specifications)
DX80...C models: IEC IP20; NEMA 1 (In a suitable en-
closure: Class I, Division 2, Group A, B, C, D; T4 −40
to 80 °C)
Conditions
Operating Temperature: −40 to +85 °C (Electronics);
−20 to +80 °C (LCD)
Operating Humidity: 95% max. relative (non-condens-
ing)
Radiated Immunity: 10 V/m, 80-2700 MHz
(EN61000-6-2)
Shock and Vibration
IEC 68-2-6 and IEC 68-2-7
Shock: 30g, 11 millisecond half sine wave, 18 shocks
Vibration: 0.5 mm p-p, 10 to 60 Hz
Refer to the
SureCross DX80 Wireless I/O Network Product Man-
ual
(p/n 132607) for installation and waterproofing instructions. Op-
erating the devices at the maximum operating conditions for exten-
ded periods can shorten the life of the device.
P/N 134323 Rev. G
Radio and General
Wiring Access
Four PG-7, One 1/2-inch NPT, One 5-pin Euro-style
male connector
For European applications, power the DX80 from a Limited Power
Source as defined in EN 60950-1.
Inputs and Outputs
Discrete Outputs
Update Rate: 125 milliseconds
ON Condition: Supply minus 2V
OFF Condition: Less than 2V
Output State Following Timeout: OFF
Discrete Output Rating (PNP)
100 mA max current at 30V dc
ON-State Saturation: Less than 3V at 100 mA
OFF-state Leakage: Less than 10 μA
Analog Outputs
Update Rate: 125 milliseconds
Accuracy: 0.1% of full scale +0.01% per °C
Resolution: 12-bit
To verify the analog input's impedance, use an Ohm meter to
measure the resistance between the analog input terminal (AIx)
and the ground (GND) terminal.
Environmental and Certifications
DX8x...C (External Wiring Terminal Models)
(Ex/A Ex nA II T4); Certificate: 1921239
cate: LCIE 10 ATEX 1012 X
UL Listing
Maximum ambient temperature: 70 °C
Mounting instructions: See document 132607
Power rating: 10 to 30V dc, UL Class 2
Enclosure environmental rating: UL Type 1
www.bannerengineering.com - tel: 763-544-3164
CSA: Class I, Division 2, Groups A, B, C, D
LCIE/ATEX: Zone 2 (II 3G / Ex nA IIC); Certifi-
7