Design And Function; Input Functionality; Sensor Redundancy; Sensor Drift Monitoring - ABB TTF300 Operating Instruction

Field-mount temperature transmitter for all communications protocols, redundancy thanks to two inputs
Hide thumbs Also See for TTF300:
Table of Contents

Advertisement

TTF300 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF300-EN REV. G

4 Design and function

TTF300 digital transmitters are communication-ready devices
with microprocessor-controlled electronics.
In the HART® transmitter, an FSK signal is superimposed on the
4 to 20 mA output signal in accordance with the HART standard
to facilitate bidirectional communication.
In the PROFIBUS PA transmitter, communication takes place in
accordance with PROFIBUS – MBP (IEC 61158-2), PROFIBUS PA
Profile 3.01.
With FF transmitters, communication takes place in accordance
with FOUNDATION Fieldbus H1 (IEC 61158-2), ITK Version 5.x.
The transmitters can be configured, queried and tested using a
DTM, an EDD, the Field Information Manager (FIM) or the
optional Type A LCD indicator.
1 Supply voltage cable
2 TTF300 transmitter
3 Temperature sensor
Figure 12: Setup
4 Process pipe
5 Sensor connection cable

Input functionality

Sensor Redundancy

To enhance system availability, the TTF300 has two sensor
inputs.
The second sensor input can be used redundantly for both
resistance thermometers (2 x three-wire circuit or 2 x two-wire
circuit) and thermocouples, or for a mixture of the two.
Sensor redundancy (or sensor backup) always involves
measuring the temperature of the two sensors and calculating
the mean value on the basis of this.
This value is provided at the output of the transmitter. Should a
sensor fail, the temperature measurement for the sensor that
remains in operation is provided at the output of the
transmitter.
A relevant diagnosis notice is available via DTM, EDD,
FDI Package (FIM) or on the LCD indicator. The measured value
remains available and maintenance measures can be taken at the
same time.

Sensor drift monitoring

When two sensors are connected, sensor drift monitoring can be
activated via the DTM, EDD or FDI Package (FIM) .
The sensor drift monitoring can be activated for the following
sensor types:
2 × resistance thermometer (RTD), two-wire circuit
2 × resistance thermometer (RTD), three-wire circuit
2 × resistors (potentiometer), two-wire circuit
2 × resistors (potentiometer), three-wire circuit
2 × thermocouple
2 × voltages
1 × resistance thermometer (RTD), two-wire circuit, and
1 × thermocouple
1 × resistance thermometer (RTD), three-wire circuit, and
1 × thermocouple
1 × resistance thermometer (RTD), four-wire circuit, and
1 × thermocouple
To activate sensor drift monitoring, the transmitter must first
be configured for the sensor types referred to above. Following
this, the maximum permissible sensor deviation must be
configured, e.g., 1 K.
Since sensor response times may differ slightly, it is then
necessary to configure a limit time period during which the
sensor deviation has to constantly exceed the maximum set.
If the transmitter records a larger sensor deviation during the
defined time period, a 'Maintenance required' diagnosis
information is generated through HART, EDD and DTM in
accordance with NE 107. At the same time, diagnostic
information is shown on the LCD indicator.
21

Advertisement

Table of Contents
loading

Table of Contents