Commissioning; Operating Instructions; Damage To The 'Flameproof (Enclosure)- Ex D' Type Of Protection; Protection Against Electrostatic Discharges - ABB TTF300 Operating Instruction

Field-mount temperature transmitter for all communications protocols, redundancy thanks to two inputs
Hide thumbs Also See for TTF300:
Table of Contents

Advertisement

16
TTF300 FIELD-MOUNT TEMPERATURE TRANSMITTER | OI/TTF300-EN REV. G
... 2 Use in potentially explosive atmospheres in accordance with
ATEX and IECEx

Commissioning

The commissioning and parameterization of the device may also
be carried out in potentially explosive atmospheres using a
handheld terminal that has been approved accordingly under
consideration of an intrinsic safety installation check.
Alternatively, an Ex modem can be connected to the circuit
outside the potentially explosive atmosphere.

Operating instructions

DANGER
Risk of explosion due to hot parts
Hot parts inside the device pose an explosion hazard.
Never open the device immediately after switch-off.
A waiting time of at least four minutes should be observed
before opening the device.
DANGER
Explosion hazard when opening the device
Explosion hazard when opening the device with activated
power supply.
Before opening the device, switch off the power supply.
Damage to the 'Flameproof (enclosure)– Ex d' type of
protection
The cover thread is used as a flameproof joint for the
'Flameproof (enclosure) – Ex d' type of protection.
During assembly / disassembly of the device, make sure that
the cover thread does not get damaged.
Devices with damaged threads must no longer be used in
potentially explosive atmospheres.

Protection against electrostatic discharges

The painted surface of the housing and the plastic parts inside
the device can store electrostatic charges.
WARNING
Risk of explosion!
The device must not be used in areas in which process-
related electrostatic charging of the housing may occur.
The device must be maintained and cleaned so that any
dangerous electrostatic charge is avoided.

Repair

DANGER
Explosion hazard
Explosion hazard due to improper repair of the device. Faulty
devices must not be repaired by the operator.
The device may only be repaired by the ABB Service
Department.
Repairs on flameproof joints are not permitted.