History Log - Bosch MAP 5000 Series Installation Manual

Hide thumbs Also See for MAP 5000 Series:
Table of Contents

Advertisement

86
en | Appendices
In case of a fault on the primary connection to a receiver, ICP-MAP5000-COM and ICP-
MAP5000-SC are connecting to a backup receiver using the alternate transmission path.
The fault on the primary path is reported to the backup receiver and displayed on the control
center.
ICP-MAP5000-COM and ICP-MAP5000-SC can report to any alarm receiver supporting the
following protocols:
Transmission path faults are directly reported to the user via the MAP 5000 control center.
ICP-MAP5000-COM and ICP-MAP5000-SC have implemented layer 1 supervision for Ethernet
and wireless path.
ICP-MAP5000-COM and ICP-MAP5000-SC supervise the link to Ethernet and poll the wireless
network on checking for connection, signal strength and sign in status.
The communicator in ICP-MAP5000-COM and ICP-MAP5000-SC is realized as a pass-through
system.
The monitoring center, to which the panel is connected to, has to provide proof of availability
of the alarm transmission system.
For information security purposes, ICP-MAP5000-COM and ICP-MAP5000-SC provide the
possibility of encrypted transmission (AES 128, 192, 256).
To grant anti-substitution security, the initial key has to be provided manually by typing it into
the configuration software RPS for MAP.
8.5

History log

The history log of the MAP 5000 panel can be configured for 1000 to 4000 entries using RPS
for MAP 5000.
For the SPT functionality, an additional history log of 1000 entries is available.
Both history logs are independent from each other and cannot influence each other.
In both history logs, the logged mandatory events cannot be deleted or overwritten by any
logged optional events.
For both history logs there is no duration defined. This means, that events are stored for an
unlimited amount of time and are not affected in case of power loss at the panel.
2019-09 | 25 | F.01U.168.332
Conettix IP
SIA DC 09
VDS 2465
Installation manual
MAP 5000
Bosch Security Systems B.V.

Advertisement

Table of Contents
loading

Table of Contents