Control Screens; Model Information - IBM 6000 VA LCD 4U Installation And Maintenance Manual

Rack ups extended battery module
Hide thumbs Also See for 6000 VA LCD 4U:
Table of Contents

Advertisement

Control screens

The following table describes the available control screens.
Table 7. Control screens
Control screen
Go to Bypass
Battery test
Reset error state
Load segments
Restore factory settings

Model information

The model information screens display the following UPS information:
v Model/Type: Chassis style and supply power rating
v MT, Product ID, SN: Machine type, product identification (model number), serial
v NMC firmware: Firmware version for the network management card
v NMC IP address: IP address for the network management card
v Comm firmware: Firmware version for the second processor on the UPS
v UPS firmware: Firmware version for the primary processor on the UPS
Note: The network management card firmware screens are displayed only if an
IBM Network Management Card is installed. See "IBM Network Management Card"
on page 33.
Description
Transfers the UPS system to internal Bypass mode.
When the Go to Bypass command is issued, the screen displays the Manual
Bypass Comment Sent message for five seconds. The option then changes to Go
to Normal.
When the Go to Normal command is issued, the screen displays the Normal Mode
Command Sent message for five seconds. The option then changes to Go to
Bypass.
Schedule Battery Test: yes | Cancel Battery test: no
Starts a manual battery test.
See "Testing a battery" on page 43.
Reset Alarms: yes | no
Manually clears any latched alarms, such as bad battery detected or DC Bus
OV/UV, and then performs a self-diagnostics test of the LCD, alarm sounds, and
fans.
If a bad battery alarm was also active, resets the battery test status to Not
Tested.
Load segment 1: on | off
Load segment 2: on | off
These on/off commands override automatic load segment on/off controls made
by the Automatic Start Delay and Automatic On Battery Shutdown settings. See
"Configuring load segments" on page 27.
Restore Factory Settings: yes | no
Available only in Standby mode.
Restoring the factory settings:
v Returns all user-configurable EEPROM settings to default factory settings
v Resets all pending on/off commands
v Clears the alarm history and resets all statistic values and time stamps
v Resets the battery test status
v Initiates the Self Diagnostics test
number
Chapter 3. Operating the uninterruptible power supply
23