IBM 6000 VA LCD 4U Installation And Maintenance Manual page 10

Rack ups extended battery module
Hide thumbs Also See for 6000 VA LCD 4U:
Table of Contents

Advertisement

CAUTION:
v Do not install a unit in a rack where the internal rack ambient temperatures
v Do not install a unit in a rack where the air flow is compromised. Ensure
v Consideration should be given to the connection of the equipment to the
v (For sliding drawers) Do not pull out or install any drawer or feature if the
v (For fixed drawers) This drawer is a fixed drawer and must not be moved
(R001 part 2 of 2)
Important:
1. To reduce the risk of fire, connect only to a circuit provided with branch circuit
2. For permanently connected equipment: Make sure that a readily accessible
3. You can connect only one extended battery module to the UPS.
4. For input voltage rating 115/200 – 127/220 V ac, the IBM 6000 VA LCD 4U
viii
6000 VA UPS and 6000 VA EBM: Installation and Maintenance Guide
will exceed the manufacturer's recommended ambient temperature for all
your rack-mounted devices.
that air flow is not blocked or reduced on any side, front, or back of a unit
used for air flow through the unit.
supply circuit so that overloading of the circuits does not compromise the
supply wiring or overcurrent protection. To provide the correct power
connection to a rack, refer to the rating labels located on the equipment in
the rack to determine the total power requirement of the supply circuit.
rack stabilizer brackets are not attached to the rack. Do not pull out more
than one drawer at a time. The rack might become unstable if you pull out
more than one drawer at a time.
for servicing unless specified by the manufacturer. Attempting to move the
drawer partially or completely out of the rack might cause the rack to
become unstable or cause the drawer to fall out of the rack.
overcurrent protection with an ampere rating in accordance with the National
Electrical Code (NEC), ANSI/NFPA 70 or your local electrical code.
UPS output power
200 V
6000 VA
40 amp, 2-pole circuit
breaker
disconnect device is incorporated in the building installation wiring.
Rack UPS (200 V / 208 V) must be connected phase-to-phase (and not
phase-to-neutral), so that the input voltage of the UPS is 200 V or 220 V.
208 V
230 V
40 amp, 2-pole circuit
32 amp (Europe), 40
breaker
amp (North America),
2-pole circuit breaker