Battery charge values without loads

The fully-charged, no-load connected battery voltages for the UPS models are
described in the following table.
The voltage values are indicated for one battery only. To measure the voltage value,
you must disconnect any batteries that are connected to each other. The battery
voltage must be measured at the battery connectors as shown in the following
illustration.
For more information about battery charge values without loads, see the Retain tip:
H202830 at http://ibm.com/support/entry/portal/docdisplay?lndocid=migr-5087624.
44
6000 VA UPS and 6000 VA EBM: Installation and Maintenance Guide
Table 13. Battery voltages
UPS
IBM 6000 VA UPS
(200 V / 208 V)
IBM 6000 VA UPS (230 V)
1 0
0 %
1 5 0
2 0 8
0
V A
6
V
/6 0
U P
h z
m
in
S O
N
O K
O K
Ground
Positive
(black)
(red)
Type-
model
Nominal
5395-6AX 108
5395-6KX 108
Battery VDC
Minimum
113.4
113.4