Configuration - IBM 6000 VA LCD 4U Installation And Maintenance Manual

Rack ups extended battery module
Hide thumbs Also See for 6000 VA LCD 4U:
Table of Contents

Advertisement

Configuration

Only the available options are displayed.
User settings are not protected by default. You can enable the password through
the User Password setting.
The following table describes the options that you can change.
Table 8. Configuration settings
Description
Available settings
Change language
[English] [French] [German] [Spanish] [Japanese] [Simplified
Chinese] [Russian] [Korean] [Traditional Chinese]
User password
[Enabled] [Disabled]
If Enabled, the default password is USER and cannot be
changed.
Note: If you enter an incorrect password, the message Wrong
Password is displayed. Press any button to return to the password
screen and retry the password.
Audible alarms
[Enabled] [Disabled]
Note: If you disable audible alarms, it takes effect instantly and
remains disabled, even after a power cycle. This differs from the
mute feature, by which the horn is temporarily silenced when any
button is pressed but turns on again if a new alarm is triggered.
Set date and time
Set Month, Day, Year, Hours, Minutes, and Seconds
Date: mm/dd/yyyy
Time: hh:mm:ss
Notes:
1. The date format is dependent on the language selection.
2. Time is a 24-hour clock.
Control commands
[Enabled] [Disabled]
from serial port
If Enabled, control commands are accepted through the serial
port, USB ports, or option card.
If Disabled, configuration and load control commands are
restricted to LCD only.
Output voltage
[Auto sensing]
[200V] [208V]
[220V] [230V] [240V]
Note: Numerical output voltage settings that are configured in
Standby mode take effect immediately. Auto sensing and any
settings that are configured outside of Standby mode take effect
after the next power off and restart. Selecting auto sensing
disables the battery start feature until after the next successful
startup on utility power.
Output frequency
[50Hz] [60Hz] [Auto sensing]
Note: Numerical output frequency settings that are configured in
Standby mode take effect immediately. Auto sensing and any
settings that are configured outside of Standby mode take effect
after the next power off and restart. Selecting auto sensing
disables the battery start feature until after the next successful
startup on utility power.
24
6000 VA UPS and 6000 VA EBM: Installation and Maintenance Guide
Default setting
English
Disabled
Enabled
01/01/2010
12:00:00
Enabled
Auto sensing
Note: The default auto
sensing runs once to set
the output voltage and
then is disabled.
Auto sensing
Note: The default auto
sensing runs once to set
the output frequency and
then is disabled.