Control screens
The following table describes the available control screens.
Table 7. Control screens
Control screen
Battery test
Reset error state
Load segments
Restore factory settings
Model information
The model information screens display the following uninterruptible power supply
information:
v Model/Type: Chassis style and supply power rating
v MT, Product ID, SN: Machine type, product identification (model number), serial
v NMC firmware: Firmware version for the network management card
v NMC IP address: IP address for the network management card
v UPS firmware: Firmware version for the uninterruptible power supply
Note: The network management card firmware screens are displayed only if an
IBM Network Management Card is installed. See "IBM Network Management Card"
on page 32.
Description
Schedule Battery Test: yes | Cancel Battery test: no
Starts a manual battery test.
See "Testing a battery" on page 39.
Reset Alarms: yes | no
Manually clears any latched alarms, such as bad battery detected or DC Bus
OV/UV, and then performs a self-diagnostics test of the LCD, alarm sounds, and
fans.
If a bad battery alarm was also active, reset the battery test status to Not Tested.
Load segment 1: on | off
Load segment 2: on | off
These on/off commands override automatic load segment on/off controls made
by the Automatic Start Delay and Automatic On Battery Shutdown settings. See
"Configuring load segments" on page 26.
Restore Factory Settings: yes | no
Available only in Standby mode.
Restoring the factory settings:
v Returns all user-configurable EEPROM settings to default factory settings
v Resets all pending on/off commands
v Clears the alarm history and resets all statistic values and time stamps
v Resets the battery test status
v Initiates the Self Diagnostics test
number
Chapter 3. Operating the uninterruptible power supply
23