Power Supply Concept; Figure 12: Power Supply Concept Gl/Lr - WAGO 750-626/xxx-xxx Manual

24v dc power supply filter filter module for system and field side power supply
Table of Contents

Advertisement

30
Connect Devices
Pos : 75 /All e Seri en (Allgemei ne Module)/Ü berschriften für alle Serien/Ansc hließ en/Eins peisekonzept - Übersc hrift 2 @ 9\mod_1292323902755_21.doc x @ 67445 @ 2 @ 1
5.2

Power Supply Concept

Pos : 76 /Serie 750 ( WAGO-I/O-SYST EM)/Ans chli eßen/Eins peisekonz epte/GL/LR Ei ns peis ekonzept 750- 0624/- 0626 @ 8\mod_1279185087861_21.doc x @ 60030 @ @ 1
The following illustration shows the power supply concept of a WAGO-I/O-
SYSTEM 750 fieldbus node for the certified application according to GL/LR.

Figure 12: Power supply concept GL/LR

The 24 V system power supply of the coupler / controller must be filtered using
the filter module 750-626 and protected against overvoltages.
The 24 V field power supplies must be protected against overvoltage using the
filter modules 750-624 or 750-626.
When supplying the ground (earth) potential via the power jumper contacts or if a
fuse protection or monitoring of the field power supply is required, a supply
module 750-601 (24 V power supply with fuse), 750-602 (24 V power supply
without fuse) or 750-610 (24 V power supply with fuse and diagnostics) should be
used in addition to the filter module 750-626.
Otherwise the use of a supply module is not required in addition to the filter
module 750-626. The downstream modules can then be directly supplied via the
power jumper contacts of the filter module 750-626.
For each additional 24 V field side power supply, a filter module 750-624 is to be
used in addition to the supply module 750-601, 750-602 or 750-610.
No filter module is required using 230 V field side power supply.