6.2

Power Supply Concept

6.2.1

Supplementary Power Supply Regulations

For certified operation in shipbuilding applications and onshore/offshore
installations as well as in the railway and energy supply areas, additional filter
modules must be used:
750-626/040-000 filter module (24 VDC HI XTR Supply Filter) for filtering
the 24 VDC field supply and the 24 VDC system supply, or
750-624/040-001 filter module (24 VDC HI NC XTR Field Supply Filter) for
filtering the 24 VDC field supply.
When the internal system supply module with fuse 750-610/040-000 (Power
Supply 24 VDC Fuse Diagn XTR) described here is used, the 750-624/040-000
filter module (24 VDC HI NC XTR Field Supply Filter) must be connected directly
after it.

Figure 11: Supply Concept