750-626 24V DC Power Supply Filter
Pos : 30 /Serie 750 ( WAGO-I/O-SYST EM)/Ger ätebesc hrei bung/Ansc hl üss e/Leistungs kontakte/F el dvers orgung - Übersc hrift 3 @ 6\mod_1256294692864_21.doc x @ 43664 @ 3 @ 1
3.2.2

Power Jumper Contacts/Field Supply

Pos : 31.1 /Serie 750 (WAGO-I/O-SYST EM)/Ger ätebesc hrei bung/Ansc hl üsse/Leistungs kontakte 2 LK (Feder) - Ei nleitung @ 15\mod_1371724414861_21.doc x @ 123722 @ @ 1
The power supply module 750-626 has 2 self-cleaning power jumper contacts that
transmit power for the field side. The contacts on the right side of the power
supply module are designed as spring contacts.
Pos : 31.2 /Serie 750 (WAGO-I/O-SYST EM)/Ger ätebesc hrei bung/Ansc hl üsse/Leistungs kontakte 2 LK (Feder) - Abbil dung - Standar d @ 15\mod_1371548903658_21.doc x @ 123408 @ @ 1

Figure 3: Power Jumper Contacts

Pos : 31.3 /Serie 750 (WAGO-I/O-SYST EM)/Ger ätebesc hrei bung/Ansc hl üsse/Leistungs kontakte 2 LK (Feder) - Legende @ 15\mod_1371724465179_21.doc x @ 123726 @ @ 1

Table 5: Legend for Figure "Power Jumper Contacts"

Contact
1
2
Pos : 31.4 /Serie 750 (WAGO-I/O-SYST EM)/Wic htige Erläuterungen/Sicherheits- und sonstig e Hinweis e/Achtung/Achtung: M axi mal er Strom Leistungs kontakte 10 A @ 3\mod_1226499143500_21.doc x @ 25029 @ @ 1
Do not exceed maximum current via power jumper contacts!
The maximum current to flow through the power jumper contacts is 10 A.
Greater currents can damage the contacts.
When configuring your system, ensure that this current is not exceeded. If
exceeded, insert an additional supply module.
Pos : 31.5 /Serie 750 (WAGO-I/O-SYST EM)/Wic htige Erläuterungen/Sicherheits- und sonstig e Hinweis e/Hinweis/Hi nweis: Potenti alei ns peis ekl emme für Erde ei nsetzen! ( kei ne LK für Erde) @ 3\mod_1226499037468_21.doc x @ 25023 @ @ 1
Use supply modules for ground (earth)!
The I/O module has no power jumper contacts for receiving and transmitting the
earth potential. Use a supply module when an earth potential is needed for the
subsequent I/O modules.
Pos : 32 /D okumentation allgemei n/Glieder ungs elemente/---Seitenwechs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
Manual
Version 1.4.0
Type
Spring contact
Spring contact
Function
Potential feed-in (Uv) for field supply
Potential feed-in (0 V) for field supply
Device Description
17

Advertisement

Chapters

Table of Contents
loading

This manual is also suitable for:

750

Table of Contents