System Errors; Stage Status; Relay Status - Intec MGC2-12 User Manual

Multi-point controller
Table of Contents

Advertisement

PolyGard
Multi-Point Controller
®
User Manual - MGC2-12
3.1.3

System Errors

System Error Messages:
SP XX > 22 mA
Cause:
Solution:
SP XX < 3 mA
Cause:
Solution:
GC Error:
Cause:
Solution:
EP 0X Com Error:
Cause:
Solution:
Maintenance:
Cause:
Solution:
3.2

Stage Status

Displays the actual stages exceeded in the sequence that they happen. The sensor point displays with the stages
that have been exceeded. Changes cannot be made in this menu.
SP 01
S1 S2
Symbol
Description
Sensor Point
SP 01
(SP) No.
SX
Stage Status
3.3

Relay Status

Display the actual status of each relay and changes can be made for manual operation of the relays.
R 01
OFF
Symbol
Description
R 01
Relay No. 01
OFF
Status Relay
Polygard® is a registered trademark of MSR
Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Current signal at analog Input XX > 22 mA.
Short-circuit at analog Input or Transmitter not calibrated, Transmitter defective.
Check cable to Transmitter, Perform Calibration, Change the Transmitter.
Current signal to analog Input XX < 3 mA.
Open circuit at analog Input or Transmitter not calibrated, Transmitter defective.
Check cable to Transmitter, Perform Calibration, Change the Transmitter.
Internal Communication Error I/O Board to LCD Board.
Internal Error.
Change the Controller.
Communication error to expansion module (EP 0X).
(Only active, if EP module announced).
EP module address not correct. (See Start up Operation 5.0)
Bus cable to EP 0X module disconnected.
No power supply at the EP 0X module.
EP module defective.
Check the EP module address.
Check the bus cable and the power supply.
Change the EP 0X module.
System maintenance is necessary.
Maintenance date exceeded.
Perform maintenance.
Function
S1 = Stage 1 ON
S2 = Stage 2 ON
S3 = Stage 3 ON
S4 = Stage 4 ON
S5 = Stage 5 ON
Setting
Function
Status
Select Relay No.
OFF
ON
OFF
Manual OFF
Manual ON
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
= Relay Off (Not Activated by Stage Setpoint)
= Relay On (Activated by Stage Setpoint)
= Relay manual Off
= Relay manual On
Specification subject to change without notice.
Page 09
MGC2-12
Printed in USA 131119