3.7.2

Software Version

Symbol
Description
GC02-
Software
XX
Version
3.7.3

Maintenance Concept

The MGC2 system monitors the maintenance intervals as required, by local Regulations or Customer
requirements.
During start-up and/or after maintenance the date for next maintenance is entered. When this date is reached at 9
o'clock the next morning a failure signal is activated and Start Menu displays the phone No. of the service
company. The failure signal (maintenance) can be acknowledged by the operator. The maintenance message
(Service Phone No.) is reset after maintenance is accomplished and a new maintenance date is entered.
The service phone number can be individually entered in the next menu.
Symbol
Description
MM.DD.YY Maintenance
8585....
Phone No.
3.7.4

Average Value Function

The Controller calculates for each active sensing point the arithmetic average value from 10 measurements within
the time unit defined in this menu "AV-time". This average value is indicated in the menu "Sensor Readings" near
the Current Value. During each Sensor Point Setup the control mode of Current Value or Average Value for the
Stage/Setpoint evaluation is defined.
The evaluation of the control mode Average Value is overlaid by the Current Value, if this exceeds Stage/Setpoint
defined in the menu "AV-Overlay". The overlay is delayed by the time factor set in this menu.
Symbol
Description
120 s
AV- Overlay
120pm
1800 s
AV-Time
3.7.5

Time, Date

Input and correction of the system time and date. Selection of the time and date format.
Symbol
Description
US
Time format
hh.mm.ss
Time
MM.DD.YY Date
Polygard® is a registered trademark of MSR
Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Default
Function
Status
XX = Software Version
Default
Function
Status
MM.DD.YY = Input date for next maintenance.
Input the individual service phone No.
Default
Function
Status
120 s
sec. = Delay time average value Overlay. 0 = No overlay Function
120 ppm
ppm = Threshold average Overlay
1800 s
sec. = Time to calculate average value
Default
Function
Status
EU = Display time and date in EU format
US
US = Display time and date in US format
hh.mm.ss = Input the correct time (EU format)
hh.mm.ss am = Input the correct time (US format)
TT.MM.JJ = Input the correct date (EU format)
MM.DD.YY = Input the correct date (US format)
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Page 21
Specification subject to change without notice.
Printed in USA 131119
MGC2-12