Acknowledge the horn relay
On
Alarm 4
Of
On
Relay 4
Off
Acknowledging
On
signal
Off
Special function „Response". (Return of the horn relay)
On
Alarm 4
Off
On
Relay 4
Off
Acknowledging-
On
signal
Off
3.5.5

External operation of Relay.

Assign one digital input (DI) for external setting of the relay ON and/or OFF. This function has priority before a
stage threshold is exceeded and/or manual switching in the menu "Relay Status".
Symbol
Description
R 01
Relay No.
DI-ON
External On
DI-OFF
External Off
3.5.6

Delay operation of Relay.

Delay ON time begins when the Stage is exceeded and/or Delay OFF time when the Stage returns to normal
condition.
Symbol
Description
R 01
Relay No.
0 s
Delay Time ON
0 s
Delay Time OFF 0
Polygard® is a registered trademark of MSR
Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Gas Concentration greater
Time
Gas Concentration greater
Time
Time
Setting
Function
Status
Selection Relay
DI
0
If digital input closed, relay switch ON
0
If digital input closed, relay switch OFF
Setting
Function
Status
Selection Relay
Stage ON: Relay is only activated at expiration of the defined
0
time (sec.) 0 sec. = No Delay
Stage OFF: Relay is only deactivated at expiration of the defined
time (sec.) 0 sec. = No Delay
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Page 13
smaller as Threshold
smaller as Threshold
Specification subject to change without notice.
MGC2-12
Printed in USA 131119