3.6

Menu SP Setup

Display and Change Parameters, Assign Stage value, Assign relays to stages and activate each Sensor Point
(SP).
SP Setup
SP 01
active
Polygard® is a registered trademark of MSR
Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
(Main Menu)
(Selection of a sensor point)
SP Mode
active
SP Type
NH3
Measuring range
300 ppm
SP-Signal
linear
Stage 1
100 ppm
Stage 2
100 ppm
Stage 3
200 ppm
Stage 4
200 ppm
Stage 5
300 ppm
Hysteresis
15 ppm
Delay ON time
0 s
Fax (858) 578-4633 & (888) FX INTEC
Activate or deactivate SP
See 3.6.1
Define Type
See 3.6.2
Define Measuring range
See 3.6.3
Define signal type of transmitter
See 3.6.4
Define Stage/Setpoint 1
See 3.6.5
Define Stage/Setpoint 2
See 3.6.5
Define Stage/Setpoint 3
See 3.6.5
Define Stage/Setpoint 4
See 3.6.5 Stage/Setpoint
Define Stage/Setpoint 5
See 3.6.5
Hysteresis
See 3.6.5
Set Delay ON time
See 3.6.6