3.7.6

Customer Password (Code 1)

Change the System Password for level 1
Symbol
Description
Customer-
1234
password
Factory preprogrammed system password "9001".
3.7.7

Analog Output

The Controller has two analog outputs (AO) with 4 to 20 mA signal per control module. Each of the six analog
outputs can be assigned the signal of one or more sensor points. The assignment occurs in the menu "SP
Setup" for each SP. The sensor point sends the signal that is defined in the menu "C/A Mode".
The Controller determines from the signal of all assigned sensor points the minimum, the maximum or the average
value and sends this value to the analog output. The determination of which value is sent is defined in this menu
"Analog Output X". The analog output can be calibrated for 4 and 20 mA using an ampere meter attached (with
measuring range 25 mA) then respective AO factor can be changed to adjust the analog output 4 and/or 20 mA
During AO calibration no evaluation is made of the sensor point signals. This calibration is factory-set. The factors
should only be changed if you have an accurate amp meter.
Symbol
Description
Select
Max.
Output mode
4.0
Calibration
20.0
3.7.8

Define the Failure Relay

Define the Failure Relay. See also malfunction management (3.1)
Symbol
Description
14
Failure Relay R14
3.7.9

Power On Time

Sensors need a warm up period until the chemical process of the sensor reaches a stable condition. During this
warm up period the current signal can cause unwanted false alarms. Therefore, the Controller starts reporting
alarms after the Power ON Time delay once power is applied. While this time runs off, the Controller does not
report alarms. The Power On status is displayed.
Symbol
Description
30 s
Power On Time
Polygard® is a registered trademark of MSR
Customer Services (858) 578-7887 & (888) GO INTEC
INTEC Controls, 12700 Stowe Dr., Suite 100, Poway, CA 92064
Default
Function
Status
1234
1234 = Define the Customer Password with 4 characters
Default
Function
Status
Min.
= Spends the minimum value of all assigned SP
Max.
Max.
= Spends the maximum value of all assigned SP
Average = Spends the average value of all assigned SP
4.0
4.0
= Calibration factor at 4 mA
20.0
20.0
= Calibration factor at 20 mA
Default
Function
Status
R14 = Define the failure relay
Default
Function
Status
30 s
XX = Define the Power On Time (sec.)
Fax (858) 578-4633 & (888) FX INTEC
www.inteccontrols.com
Page 22
Specification subject to change without notice.
Printed in USA 131119
MGC2-12