Global Options
23 - User Code Pulse
Entering a user code which has an associated user output will cause
the output to activate for the duration of the door strike timer.
User Code Latch
Entering a user code which has an associated user output will cause
the output to toggle from off to on or from on to off.
24 - Timed Test Call
A test call to the Alarm Receiving Centre will occur every time the
'Test Call Every' timer expires.
Test Call = CT4
A test call to the Alarm Receiving Centre will occur every time
'Control Timer 4' activates.
25 - Batt Test Timed
A battery test will occur every time the 'Batt Test Period' timer
expires.
Batt Test = Disarm
A battery test will occur every time the system is disarmed or after the
'Batt Test Period' timer has expired (whichever occurs first).
26 - Bell = 1st Alarm
The 'Bell' and 'Strobe' outputs will activate after an Intruder alarm (1st
Alarm) occurs.
Bell = 2nd Alarm
The 'Bell' and 'Strobe' outputs will activate after a Confirmed alarm
(2nd Alarm) occurs.
27 - SNDR = 1st Alarm
The internal sounders will sound after an Intruder alarm (1st Alarm)
occurs.
SNDR = 2nd Alarm
The internal sounders will sound after a Confirmed alarm (2nd Alarm)
occurs.
28 - Conf. = Instant
Following the arming of the system/area, if two zones activate
(causing a Confirmed alarm), the signal will be reported to the Alarm
Receiving Centre immediately.
Conf. = Delayed
Following the arming of the system/area, if two zones activate
(causing a Confirmed alarm), the signal will only be reported to the
Alarm Receiving Centre after the 'Abort' time has expired.
29 - Abort=Eng.Reset
An Intruder alarm that is aborted can only be reset by an
Engineer/Anti-code.
Abort=User Reset
An Intruder alarm that is aborted can be reset by any User.
30 – Auto AV Output
When using the AV Module, if a microphone is remotely selected, the
corresponding output automatically activates.
Manual AV Output
When using the AV Module, if a microphone is remotely selected, the
corresponding output must be activated manually.
31 - Clock = 50Hz
The internal clock on the control panel runs from the 50Hz main
frequency.
Clock = Crystal
The internal clock on the control panel runs from the built-in crystal.
32 - 80 Column Print
Select this option when connecting an 80 Column printer to the
control panel.
40 Column Print
Select this option when connecting an 40 Column printer to the
control panel.
33 - Disable Text
Areas that are armed are displayed as letters on the bottom line of
the display i.e. 'Armed: AB.D...'
Enable Text
Areas that are armed are displayed using their assigned text on the
bottom line of the display i.e. 'Armed: Garage', 'Office' etc. (a
different area is displayed every second).
72
Premier Elite Series Installation Manual
34 - EN50131 Enabled
Keypad display 'blanking' is enabled i.e. the keypad will only display
the time, date and the banner message. If information is available to
be viewed i.e. AC Mains Fail, Line Fault, System Faults etc. the
keypad will bleep every 30 seconds and display 'System Alerts', this
information can only be viewed after a valid user code has been
entered. The keypad display will then 'blank' again 30 seconds after.
The bell output will not activate, if an alarm occurs during the entry
mode.
EN50131 Disabled
The Control Panels EN50131 options are disabled.
Duress Codes can only be programmed by an engineer
35 - 1st Zone = Confirm
After the entry timer has expired, activation of 1 more zone is required
to generate a Confirmed alarm.
2nd Zone = Confirm
After the entry timer has expired, activation of 2 more zones is required
to generate a Confirmed alarm
36 - Keypads Global
Keypads show information for all areas.
Keypads Local
Keypads only show information that is relative to the area that the
keypad is assigned to.
37 - Panel Grade 2
All options relating to PD6662: 2004/EN 50131-1 Grade 3 that are not
required for Grade 2 are disabled automatically. Also, the Anti-code reset
becomes the standard 4 digit number and all user and engineer codes
can be 4, 5 or 6 digits.
Panel Grade 3
All options relating to PD6662: 2004/EN 50131-1 Grade 3 are enabled
automatically. Also, the Anti-code reset becomes a 6-digit number
and all user codes can only be programmed as 5 or 6 digits.
38 - Disable FOB PA
When a 'Smartkey' Transmitter FOB is being used with the alarm
system, the Panic Alarm (PA) function i.e. Pressing buttons 1 and 2
together, is disabled.
Enable RF FOB PA
When a 'Smartkey' Transmitter FOB is being used with the alarm
system, the Panic Alarm (PA) function i.e. Pressing buttons 1 and 2
together, is enabled.
39 - Armed Mask=Fault
If an Anti-masking signal is detected when the system is armed, the
control panel will generate a Fault response.
Armed Mask=Alarm
If an Anti-masking signal is detected when the system is armed, the
control panel will generate an Alarm response.
40 - Audible FOB PA
PA alarms generated from a wireless FOB will cause a Audible alarm.
Silent RF FOB PA
PA alarms generated from a wireless FOB will cause a silent alarm.
41 – Monitor PSU Battery
Battery faults from the PSU200XP are monitored.
No PSU Batt Flts
Battery faults from the PSU200XP are not monitored.
42 – Exp Loss Tamp
An expander lost event will generate a tamper alarm. Any zones
programmed on the expander will also report a tamper and alarm
condition, and if configured to do so will generate or contribute to a
Confirmed Alarm.
No Exp Loss Tamp
An expander lost event will generate a tamper/fault condition,
however any zones used will not be reported as tamper and alarm.
43 – Soak Test Warn
If zones have been placed on Soak Test, a warning will be shown to
the user at the time of arming.
INS176-15